Data sheet | Item number: 857-152 Basic relay; Nominal input voltage: 24 VDC; 1 changeover contact; Limiting continuous current: 6 A; Module width: 5 mm; Module height: 15 mm www.wago.com/857-152 Similiar to picture DC load limit curve Item description Note: 06.12.
Data sheet | Item number: 857-152 www.wago.com/857-152 Note: The 60 VDC spare relays must be used for 60 VDC, 110 VDC, 220 VDC and 115 VAC/DC, 230 VAC/DC relay modules. Inductive loads have to be attenuated by an appropriate protective circuit in order to protect relay coils and contacts. In the case of gold-plated elementary relays switching voltages of 30 VDC and currents of 50 mA should not be exceeded. Higher switching power eventually evaporates the gold layer.
Data sheet | Item number: 857-152 www.wago.com/857-152 Depth 28 mm / 1.09 inch Mechanical data Type of mounting Pluggable module Material Data Weight 4.821 g Environmental Requirements Surrounding air (operating) temperature at UN -40 … 85 °C Surrounding air (storage) temperature -40 … 85 °C Standards and specifications Standards/specifications EN 61810-1, EN 61373; VDE, UR Commercial data Country of origin DE GTIN 4045454550998 Customs Tariff No.
Data sheet | Item number: 857-152 www.wago.com/857-152 Compatible products General accessories Item no.: 857-104 Socket without relay; 24 V AC/DC www.wago.com/857-104 Downloads Documentation Bid Text 857-152 Mar 9, 2016 Zubehör Serie 857 DOC 22.5 kB Download Additional Information Disposal; Electrical and electronic equipment, Packaging Oct 15, 2018 Download 265.8 kB Device Files Device Driver WAGO 857 Series Device DTM 1.02.0007 Feb 29, 2012 ZIP 4.