Data Sheet
Data sheet | Item number:859-302
www.wago.com/859-302
06.12.2018Page /2 9
through of common input and output potentials.
A robust design and vibration-proof CAGE CLAMP spring pressure connection technology ensure continuous and uninterrupted operation for any
®
system.
Note:
Inductive loads have to be attenuated by an appropriate protective circuit in order to protect relay coils and contacts.
Data
Technical Data
Control circuit
Nominal input voltage U
N
5 VDC
Input voltage range -15 … +20 %
Nominal input current at U
N
31 mA
Load circuit:
Number of changeover/switchover contacts 1
Contact material (relay) AgSnO
2
Limiting continuous current 5 A
Max. make current (resistive) 4 s 10 A (AC)
Max. switching voltage 250 VAC
Max. switching power (resistive) 1250 VAAC; DC see load limit curve
Recommended minimum load 10 V / 10 mA; 24 V / 1 mA
Pull-in time (typ.) 8 ms
Drop-out time (typ.) 4 ms
Bounce time (typ) 5 ms
Electrical life (N.O.; resistive load; 23 °C)
50 x 10 switching operations
3
Mechanical life (N.O.; resistive load; 23 °C)
5 x 10 switching operations
6
Max. switching load with load/without load
6 min / 180 min
-1 -1
Signaling
Status indication LED red
Safety and protection:
Rated voltage 250 V
Rated impulse voltage 4 kV
Pollution degree 2
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms