Technical data
14  •  The WAGO-I/O-SYSTEM 750 
 Technical Data 
 WAGO-I/O-SYSTEM 750 
 INTERBUS 
Safe electrical isolation 
Air and creepage distance  acc. to IEC 60664-1 
Degree of pollution 
acc. To IEC 61131-2 
2 
Degree of protection 
Degree of protection  IP 20 
Electromagnetic compatibility 
Immunity to interference for industrial areas acc. to EN 61000-6-2 (2001) 
Test specification  Test values  Strength 
class 
Evaluation 
criteria 
EN 61000-4-2 ESD  4 kV/8 kV (contact/air)  2/3  B 
EN 61000-4-3 
electromagnetic fields 
10 V/m 80 MHz ... 1 GHz  3  A 
EN 61000-4-4 burst  1 kV/2 kV (data/supply)  2/3  B 
-/- (line/line)   Data: 
1 kV (line/earth)  2 
B 
0.5 kV (line/line)  1 DC 
supply: 
0.5 kV (line/earth)  1 
B 
1 kV (line/line)  2 
EN 61000-4-5 surge 
AC 
supply: 
2 kV (line/earth)  3 
B 
EN 61000-4-6 
RF disturbances 
10 V/m 80 % AM 
(0.15 ... 80 MHz) 
3 A 
Emission of interference for industrial areas acc. to EN 61000-6-4 (2001) 
Test specification  Limit values/[QP]*) Frequency range  Distance 
79 dB (μV)  150 kHz ... 500 kHz   EN 55011 (AC supply, 
conducted) 
73 dB (μV)  500 kHz ... 30 MHz   
40 dB (μV/m)  30 MHz ... 230 MHz  10 m EN 55011 (radiated) 
47 dB (μV/m)  230 MHz ... 1 GHz  10 m 
Emission of interference for residential areas acc. to EN 61000-6-3 (2001) 
Test specification  Limit values/[QP]*) Frequency range  Distance 
66 ... 56 dB (μV)  150 kHz ... 500 kHz   
56 dB (μV)  500 kHz ... 5 MHz   
EN 55022 (AC supply, 
conducted) 
60 dB (μV)  5 MHz ... 30 MHz   
40 ... 30 dB (μA)  150 kHz ... 500 kHz   EN 55022 (DC supply/data, 
conducted) 
30 dB (μA)  500 kHz ... 30 MHz   
30 dB (μV/m)  30 MHz ... 230 MHz  10 m EN 55022 (radiated) 
37 dB (μV/m)  230 MHz ... 1 GHz  10 m 