Technical data
    30BTechnical Condition of Specified Devices  • 15 
  Carrier Rail Properties 
WAGO-I/O-SYSTEM 750     
INTERBUS 
Mechanical strength acc. to IEC 61131-2 
Test specification  Frequency range  Limit value 
5 Hz  f < 9 Hz 
1.75 mm amplitude (permanent) 
3.5 mm amplitude (short term) 
9 Hz  f < 150 Hz 
0.5 g (permanent) 
1 g (short term) 
IEC 60068-2-6 vibration 
Note on vibration test: 
a) Frequency change: max. 1 octave/minute 
b) Vibration direction: 3 axes 
 15 g IEC 60068-2-27 shock 
Note on shock test: 
a) Type of shock: half sine 
b) Shock duration: 11 ms 
c) Shock direction: 3x in positive and 3x in negative 
direction for each of the three mutually perpendicular axes 
of the test specimen 
IEC 60068-2-32 free fall    1 m 
(module in original packing) 
*) QP: Quasi Peak 
Note 
If the technical data of components differ from the values described here, the 
technical data shown in the manuals of the respective components shall be 
valid. 