Technical data
28  •  The WAGO-I/O-SYSTEM 750 
 Mechanical Setup 
 WAGO-I/O-SYSTEM 750 
 INTERBUS 
2.6.9 Wire Connection 
All components have CAGE CLAMP® connections. 
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded 
and finely stranded conductors. Each clamping unit accommodates one 
conductor. 
Fig. 2-9: CAGE CLAMP® Connection  g0xxx08x 
The operating tool is inserted into the opening above the connection. This 
opens the CAGE CLAMP
®
. Subsequently the conductor can be inserted into 
the opening. After removing the operating tool, the conductor is safely 
clamped. 
More than one conductor per connection is not permissible. If several 
conductors have to be made at one connection point, then they should be made 
away from the connection point using WAGO Terminal Blocks. The terminal 
blocks may be jumpered together and a single wire brought back to the I/O 
module connection point. 
Attention 
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be used 
to join the wires together. 
Ferrule: 
 Length      8 mm 
 Nominal cross section 
max.
 1 mm
2
 for 2 conductors with 0.5 mm
2
 each 
 WAGO Product    216-103 or products with comparable properties 