Technical data
  System Supply  • 31 
  Alignment 
WAGO-I/O-SYSTEM 750     
INTERBUS 
Attention 
Resetting the system by switching on and off the system supply, must take 
place simultaneously for all supply modules (coupler/controller and 750-613).
2.7.2.2 Alignment 
Recommendation 
A stable network supply cannot be taken for granted always and everywhere. 
Therefore, regulated power supply units should be used in order to guarantee 
the quality of the supply voltage. 
The supply capacity of the coupler/controller or the internal system supply 
module (750-613) can be taken from the technical data of the components. 
Internal current consumption
*)
Current consumption via system voltage: 
5 V for electronics of the bus modules and 
coupler/controller 
Residual current for bus 
terminals
*)
Available current for the bus modules. Provided by 
the bus power supply unit. See coupler/controller 
and internal system supply module (750-613) 
*)
 cf. catalogue W4 Volume 3, manuals or internet 
Example Coupler 750-301: 
internal current consumption:350 mA at 5 V 
residual current for 
bus modules :    1650 mA at 5 V 
sum I
(5V)
total
 :    2000 mA at 5 V 
The internal current consumption is indicated in the technical data for each bus 
terminal. In order to determine the overall requirement, add together the 
values of all bus modules in the node. 
Attention 
If the sum of the internal current consumption exceeds the residual current 
f
or bus modules, then an internal system supply module (750-613) must be 
placed before the module where the permissible residual current was 
exceeded. 