Technical data
    Power Supply Unit  • 39 
  Fusing 
WAGO-I/O-SYSTEM 750     
INTERBUS 
2.7.6  Power Supply Unit 
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply 
with a maximum deviation of -15 % or +20 %. 
Recommendation 
A stable network supply cannot be taken for granted always and everywhere. 
Therefore, regulated power supply units should be used in order to guarantee 
the quality of the supply voltage. 
A buffer (200 µF per 1 A current load) should be provided for brief voltage 
dips. The I/O system buffers for approx 1 ms. 
The electrical requirement for the field supply is to be determined individually 
for each power supply point. Thereby all loads through the field devices and 
bus modules should be considered. The field supply as well influences the bus 
modules, as the inputs and outputs of some bus modules require the voltage of 
the field supply. 
Attention 
The system supply and the field supply should be isolated from the power 
supplies in order to ensure bus operation in the event of short circuits on the 
actuator side. 
WAGO products 
Item No. 
Description 
787-612  Primary switched mode; DC 24 V; 2,5 A 
Input nominal voltage AC 230 V 
787-622  Primary switched mode; DC 24 V; 5 A 
Input nominal voltage AC 230 V 
787-632  Primary switched mode; DC 24 V; 10 A 
Input nominal voltage AC 230/115 V 
288-809 
288-810 
288-812 
288-813 
Rail-mounted modules with universal mounting carrier 
AC 115 V / DC 24 V; 0,5 A 
AC 230 V / DC 24 V; 0,5 A 
AC 230 V / DC 24 V; 2 A 
AC 115 V / DC 24 V; 2 A 