Technical data
70  •  Feldbus Coupler 750-344 / -345 
 LED Indication 
 WAGO-I/O-SYSTEM 750 
 INTERBUS 
3.1.7 LED Indication 
For the on-site diagnostics the coupler has five LEDs, which display the 
operating status of the coupler or the complete node. 
Fig. 3-10: Indicators 750-344  g012232x 
3.1.7.1 Fieldbus status 
The fieldbus status is indicated by the four LEDs READY, BA, RC and RD: 
LED  Color  Status  Meaning 
READY 
Ready for 
operation 
green ON 
OFF 
Power supply within acceptable tolerance range, 
device is ready for operation 
Device not ready for operation, insufficient power 
supply 
BA 
Bus Active 
green ON 
BLINKS 
OFF 
Bus is active, data transmission taking place 
INTERBUS controller has active configuration, 
data transmission not yet started 
Bus not active, no data transmission 
RC 
Remote 
Connected 
green ON 
OFF 
Incoming interface connected, bus reset for master 
is inactive 
Bus reset is active, or interface not connected 
properly 
RD 
Remote 
Disconnected 
yellow ON 
OFF 
Transferring remote bus (outgoing interface) de-
activated 
Transferring remote bus not in use or not switched 
on 
3.1.7.2 Blink Code 
Detailed error messages are indicated by blinking codes; an error is indicated 
cyclically by up to 3 blinking sequences. An error is indicated cyclically by up 
to 3 blinking sequences. 
  The error display starts with the first blinking sequence (approx. 10 Hz). 
  After a short break, the second blinking sequence starts (approx. 1 Hz). 
The number of light pulses indicates the error code. 
  After another break, the third blinking sequence starts (approx. 1 Hz). The 
number of light pulses indicates the error argument. 