Technical data
    Feldbus Coupler 750-344 / -345  • 71 
  LED Indication 
WAGO-I/O-SYSTEM 750     
INTERBUS 
3.1.7.3 Node Status 
The I/O-LED indicates the operation of the node and signals faults occurring. 
I/O  Meaning 
green  Data cycle on the internal bus 
Off  No data cycle on the internal bus 
red  Hardware defect in the coupler 
red 
flashing 
During runup: Internal bus initialized 
During operation: General internal bus error 
red 
flashing cycle 
Fault message during internal bus reset and internal fault 
orange  I/O LED lights up orange during an update of the bus coupler 
firmware. The color orange cannot be indicated during normal 
operation. 
Coupler boot-up occurs after switching on the power supply. While doing so, 
the I/O LED flashes red. In the case of an error the I/O LED continues 
blinking red. 
In the event of error, the I/O LED continues to flash red. The error is indicated 
by the blink code cycle. 
Supply voltage
switch on
Coupler start
“I/O” LED is blinking red
Error
No
Yes
“I/O” LED
is shining green
Fieldbus start
“I/O”LED
1st flash sequence
(Introduction of the error indication)
1st pause
“I/O” LED
2nd flash sequence
Error code (number of flash cycles)
“I/O” LED
3rd flash sequence
Error argument (number of flash cycles)
2nd pause
Fig. 3-11: Signaling the node status  g012118d 