Technical data
    Feldbus Coupler 750-344 / -345  • 73 
  LED Indication 
WAGO-I/O-SYSTEM 750     
INTERBUS 
Error 
Argument 
Error description  Solution 
Error code 4: data error internal data bus 
0  Data error on data bus, data bus 
disrupted downstream of coupler. 
Switch off the power for the 
coupler. Connect the module 
downcircuit of the coupler, or 
replace the existing coupler and 
switch the power back on. 
n* (n>0)  Data bus disruption downstream of 
modules. 
Switch off the power for the 
coupler. Replace the nth module 
and switch power back on. 
Error code 5: error in register communication 
n*  Internal data bus error during 
register communication with I/O 
modules. 
Switch off the power for the 
coupler. Replace the nth module 
and switch power back on. 
* The number of light pulses (n) indicates the position of the I/O module. I/O modules 
without data are not counted (e.g. supply modules without diagnostics). 
Example: The 13th module is removed 
1.  The "I/O" LED starts the error display with the first blinking sequence (approx. 10 
Hz). 
2.  After the first break, the second blinking sequence starts (approx. 1 Hz). The I/O LED 
blinks four times, thus indicating error code 4 (data error internal bus). 
3.  After the second break, the third blink sequence starts. The I/O LED blinks twelve 
times. Error argument 12 means that the internal bus is disrupted behind the 12th I/O 
module. 