Technical data
74  •  Feldbus Coupler 750-344 / -345 
 Fault behavior 
 WAGO-I/O-SYSTEM 750 
 INTERBUS 
3.1.8 Fault behavior 
3.1.8.1 Loss of fieldbus 
A fieldbus failure is indicated, for example, if the master is switched off or if 
the bus cable is interrupted. An error at the master can also result in a fieldbus 
failure. 
On a failure of the fieldbus, the green BA LED goes out and the coupler de-
activates all outputs. 
Substitute value  Value (bit orientated) 
Digital Output Modules 
Value (byte orientated) 
Analog Output Modules 
Minimum value  0  0 and 4 mA, -10 and 0 V 
Stop internal bus  Response determined by the I/O module 
All values in the output process image are set to 0 by the coupler. With I/O 
modules that have a byte orientated data width (e.g. pulse width module), the 
substitute value is determined using the value range. 
As soon as the fieldbus is reactivated, the process data is transmitted again and 
the outputs of the node are set accordingly. 
3.1.8.2 Internal bus failure 
An internal bus failure occurs, for example, if a bus m
odule is removed. If the 
error occurs during operation, the output modules operate as they do during an 
internal bus stop: The input process image is reset and the bus coupler reports 
a periphery error to the master. 
The I/O LED flashes red. The bus coupler generates a detailed diagnostic 
message. 
After the internal bus error has been eliminated, the coupler is restarted 
automatically. The process data is transmitted again and the outputs of the 
node are set accordingly. 