Technical data
4 •  Use in Hazardous Environments 
 Identification 
 WAGO-I/O-SYSTEM 750  
Table 2: Description of the inscription 
Inscription text  Description 
TÜV 07 ATEX 554086 X 
TUN 09.0001X 
Approving authority or 
certificate numbers 
Dust 
II  Device group: All except mining 
3(1)D  Device category: Zone 22 device (Zone 20 subunit) 
Ex  Explosion protection mark 
tD  Protection by enclosure 
[iaD]  Approved in accordance with "Dust intrinsic safety" 
standard 
A22  Surface temperature determined according to 
Procedure A, use in Zone 22 
IP6X  Dust-tight (totally protected against dust) 
T 135°C  Max. surface temp. of the enclosure (no dust bin) 
Mining 
I  Device group: Mining 
(M2)  Device category: High degree of safety 
[Ex ia]  Explosion protection: Mark with category of type of 
protection intrinsic safety: Even safe when two 
errors occur 
I  Device group: Mining 
Gases 
II  Device group: All except mining 
3(1)G  Device category: Zone 2 device (Zone 0 subunit) 
Ex  Explosion protection mark 
nA  Type of protection: Non-sparking operating 
equipment 
[ia]  Category of type of protection intrinsic safety: Even 
safe when two errors occur 
IIC Explosion Group 
T4  Temperature class: Max. surface temperature 135°C 