Technical data
8 •  Use in Hazardous Environments 
 Installation Regulations 
 WAGO-I/O-SYSTEM 750  
 Special conditions for safe use (ATEX Certificate TÜV 07 
ATEX 554086 X) 
1.  For use as Gc- or Dc-apparatus (in zone 2 or 22) the field bus independent 
I/O modules WAGO-I/O-SYSTEM 750-*** shall be erected in an enclosure 
that fulfils the requirements of the applicable standards (see the marking) 
EN 60079-0, EN 60079-11, EN 60079-15, EN 61241-0 and EN 61241-1. 
For use as group I, electrical apparatus M2, the apparatus shall be erected in 
an enclosure that ensures a sufficient protection according to EN 60079-0 
and EN 60079-1 and the degree of protection IP64. The compliance of these 
requirements and the correct installation into an enclosure or a control 
cabinet of the devices shall be certified by an ExNB. 
2.  If the interface circuits are operated without the field bus coupler station 
type 750-3../…-… (DEMKO 08 ATEX 142851 X), measures must be taken 
outside of the device so that the rating voltage is not being exceeded of 
more than 40% because of transient disturbances. 
3.  DIP-switches, binary-switches and potentiometers, connected to the module 
may only be actuated when explosive atmosphere can be excluded. 
4.  The connecting and disconnecting of the non-intrinsically safe circuits is 
only permitted during installation, for maintenance or for repair purposes. 
The temporal coincidence of explosion hazardous atmosphere and 
installation, maintenance resp. repair purposes shall be excluded. 
5.  For the types 750-606, 750-625/000-001, 750-487/003-000, 750-484 the 
following shall be considered: The interface circuits shall be limited to 
overvoltage category I/II/III (non mains/mains circuits) as defined in IEC 
60664-1. 
6.  For the type 750-601 the following shall be considered: Do not remove or 
replace the fuse when the apparatus is energized. 
7.  The ambient temperature range is: 0°C ≤ T
a
 ≤ +55°C (for extended details 
please note certificate). 