Technical data

Input for thermocouple modules 750-462,469
:$*2Ç,2 Ç6<67(0
1
Input for Thermocouple Modules
PN 750-462, 750-469, 750-462/000-XXX
Technical description:
This description is only intended for hardware version X X X X 2 A 0 1 - - - -. The
serial number can be found on the right side of the module.
The following description is preliminary and is applicable only to the factory
configuration.
The shield is connected to „S“. The connection is made automatically when snapped
onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power
supply is made by the data contacts with a DC-DC converter. The modules can work
self-supporting.
Attention:
The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)!
A module which needs all contacts (e.g. 2 channel digital) may not be connected to the
right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel
modules).
The thermocouple module can be connected to all buscouplers of the
:$*2Ç,2Ç6<67(0 (except for the economy type)