Users Manual
Table Of Contents
- Table of Contents
- 1 Provisions
- 2 Safety
- 3 Overview
- 4 Properties
- 5 Functions
- 6 Planning
- 7 Transport and Storage
- 8 Installation and Removal
- 9 Connection
- 10 Commissioning
- 10.1 Setting an IP Address
- 10.2 Parameterization
- 10.2.1 PROFINET
- 10.2.2 WAGO Webserver I/O Field
- 10.2.2.1 Opening WAGO Webserver I/O Field
- 10.2.2.2 WAGO Webserver I/O Field User Interface
- 10.2.2.3 Opening the Product Information via WAGO Webserver I/O Field
- 10.2.2.3.1 Displaying Port Information
- 10.2.2.3.2 Displaying Measured Values and Information on Connected IO-Link Devices
- 10.2.2.3.3 Displaying Port Status Information
- 10.2.2.3.4 State
- 10.2.2.3.5 Quality
- 10.2.2.3.6 Revision ID
- 10.2.2.3.7 Baud Rate
- 10.2.2.3.8 Cycle Time
- 10.2.2.3.9 Input Data Length
- 10.2.2.3.10 Output Data Length
- 10.2.2.3.11 Vendor ID
- 10.2.2.3.12 Device ID
- 10.2.2.3.13 Displaying Process Data
- 10.2.2.4 Parameterizing the Product via WAGO Webserver I/O Field
- 10.2.2.4.1 Accessing a Connected IO-Link Device
- 10.2.2.4.2 Configuring Ports
- 10.2.2.4.3 Configuring IP Parameters
- 10.2.2.4.4 Storing Maintenance Information
- 10.2.2.4.5 Updating Firmware
- 10.2.2.4.6 Resetsetting the Module to the Factory Settings
- 10.2.2.4.7 Configure Bluetooth
- 10.2.2.4.8 Logging Users on and off and Managing Them
- 10.2.2.4.9 Forcing Digital Inputs and Outputs
- 10.2.2.4.10 Forcing IO-Link ports
- 10.2.3 WAGO IO-Link Configurator
- 10.2.3.1 System Requirements
- 10.2.3.2 Launching WAGO IO-Link Configurator
- 10.2.3.3 WAGO IO-Link Configurator User Interface
- 10.2.3.4 Parameterizing the Product with WAGO IO-Link Configurator
- 10.2.4 WAGO I/O Field app
- 10.2.5 OPC UA Server
- 11 Diagnostics
- 12 Service
- 13 Decommissioning
- 14 Appendix
- List of Tables
- List of Figures
765-4102/0100-0000 Properties
Product manual | Version: 2.1.0 21
8PORT IOL-B FLD PN DC 24V 2.0A
Number of subscriptions per session 2
Number of “monitored items” per session 20
Data encoding UA binary
Bluetooth Transmitter
Modulation GFSK
Data rate 1 Mbit/s
Work frequency 2402 ... 2480 MHz
Maximum power including tune up tolerance Output power: +8 dBm
Tolerance: +2 dBm / –3 dBm
Antenna type PCB monopole
Maximum antenna gain 1.25 dBi
We declare that we meet the EN62479 standard with respect to the limiting value for low
powers less than 20mW. Therefore, the product fundamentally corresponds to the Euro-
pean limiting values for high-frequency radiation.
4.5 Derating
Please note the derating for use of the product. The surrounding air temperature and the
current affect the product’s heat generation.
The derating curve was created with the following conditions of use: “without air move-
ment and with 0.5 m/s air movement” and “mounting on wall with poor heat conductivity.”
The real conditions of use may lead to better heat dissipation from the product, e.g. due
to greater air movement or better dissipation of heat to the mounting wall. The product
provides measured values for temperature and current, which you can display with
WAGO Webserver I/O Field or read out via OPC UA.
The following figure shows the maximum permissible current (I) that can flow into the
product as a function of the surrounding air temperature (T).
15
20
25
30
20
T
[°C]
25 30 35 40 45 50 55 60 65 70
I
[A]
0,5 m/s
0 m/s
Figure3: Derating, 0765-4102/0100-0000
4.6 Regulations and Standards
The following regulations and standards were used in the development of the module:
Table 17: Standards and Regulations
Standard Title
EN 61000-6-2 Electromagnetic compatibility (EMC) – Immunity for industrial en-
vironments