Users Manual
Table Of Contents
- Table of Contents
- 1 Provisions
- 2 Safety
- 3 Overview
- 4 Properties
- 5 Functions
- 6 Planning
- 7 Transport and Storage
- 8 Installation and Removal
- 9 Connection
- 10 Commissioning
- 10.1 Setting an IP Address
- 10.2 Parameterization
- 10.2.1 PROFINET
- 10.2.2 WAGO Webserver I/O Field
- 10.2.2.1 Opening WAGO Webserver I/O Field
- 10.2.2.2 WAGO Webserver I/O Field User Interface
- 10.2.2.3 Opening the Product Information via WAGO Webserver I/O Field
- 10.2.2.3.1 Displaying Port Information
- 10.2.2.3.2 Displaying Measured Values and Information on Connected IO-Link Devices
- 10.2.2.3.3 Displaying Port Status Information
- 10.2.2.3.4 State
- 10.2.2.3.5 Quality
- 10.2.2.3.6 Revision ID
- 10.2.2.3.7 Baud Rate
- 10.2.2.3.8 Cycle Time
- 10.2.2.3.9 Input Data Length
- 10.2.2.3.10 Output Data Length
- 10.2.2.3.11 Vendor ID
- 10.2.2.3.12 Device ID
- 10.2.2.3.13 Displaying Process Data
- 10.2.2.4 Parameterizing the Product via WAGO Webserver I/O Field
- 10.2.2.4.1 Accessing a Connected IO-Link Device
- 10.2.2.4.2 Configuring Ports
- 10.2.2.4.3 Configuring IP Parameters
- 10.2.2.4.4 Storing Maintenance Information
- 10.2.2.4.5 Updating Firmware
- 10.2.2.4.6 Resetsetting the Module to the Factory Settings
- 10.2.2.4.7 Configure Bluetooth
- 10.2.2.4.8 Logging Users on and off and Managing Them
- 10.2.2.4.9 Forcing Digital Inputs and Outputs
- 10.2.2.4.10 Forcing IO-Link ports
- 10.2.3 WAGO IO-Link Configurator
- 10.2.3.1 System Requirements
- 10.2.3.2 Launching WAGO IO-Link Configurator
- 10.2.3.3 WAGO IO-Link Configurator User Interface
- 10.2.3.4 Parameterizing the Product with WAGO IO-Link Configurator
- 10.2.4 WAGO I/O Field app
- 10.2.5 OPC UA Server
- 11 Diagnostics
- 12 Service
- 13 Decommissioning
- 14 Appendix
- List of Tables
- List of Figures
765-4102/0100-0000Commissioning
82 Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
PortCycleTime Drop-Down Menu
Depending on the selected operating mode, the expected cycle time of the port either can
be selected from the PortCycleTime drop-down menu or is merely displayed. The en-
coding corresponds to the one in the port status.
10.2.2.4.3 Configuring IP Parameters
Figure21: Settings Menu Item, Device Configuration Tab
The Device configuration tab shows the following parameters for the IP protocol. The
Webserver cannot configure these since they are set via the PROFINET connection:
Table 52: Device Configuration Tab – Parameter Overview
Parameters Settings/Action
Device IP address IP address for the PROFINET configuration with static
IP address configuration
Subnet mask Subnet mask for the PROFINET configuration with
static IP address configuration
Gateway IP address Gateway IP address for the PROFINET configuration
with static IP address configuration
10.2.2.4.4 Storing Maintenance Information
On the Maintenance information tab, you can store maintenance information, such as
the device name, the installation location and date, contact information, a description text
or the date of the last and next product service.