Instruction manual
25
5.6 WM1 and WM2 Menu
The Water Meter 1 and 2 menus are used to set up the type of meter and how to convert the water meter
signal into volume. The Water Meter menus will be indicated on the display as follows:
WM1 100 Gal or Liters
Reset Total
This allows you to restart the totalizer display. Press the Up or Down arrow key to change the N to Y and
press ENTER to reset the totalizer to 0 gal. The totalizer will count up to a maximum of 99,999,999.
After that it will reset itself to zero.
Vol/cont
Only appears if the Aux
relay is set to Feed on Water
Contactor
This allows you to set the volume of makeup per contact from the water meter.
K Factor
Only appears if the Aux
relay is set to Feed on
Paddlewheel
Enter the number of pulses per unit volume that the paddlewheel sensor sends out. This value is usually
printed on the sensor’s flow cell or in its instructions.
Tot Units
This is used to set the units of measure for the totalizer. Press ENTER, then use the up and down arrow
keys to toggle between "Gallons" and "Liters." Press ENTER when the desired choice is displayed.
Figure 13 WM1 and WM2 Menu
WM1 1000Gal
Reset Total N
1000 S 68° F
WM1 1000Gal
WM1 1000Gal
Tot Units Gal
WM1 and WM2 Menus
ENTEREXIT
NEXTPREV.
Legend
1
Menu choice appears if WM Type is Water Contactor
Menu choice appears if WM T
y
pe is Paddlewheel
WM1 1000Gal
KFactor 999.9
2
Tot Units Gal
Gallons
ENTEREXIT
Tot Units Gal
Liters
WM1 1000Gal
Gal/Cont. 10
1
or
WM1 1000Gal
Lit/Cont. 10
2