Operating Manual Light Control “PULSE PIR - Vers. IV with MFT”
ENG
Changing basic settings - Part 1
Change to 
parameterisation mode
Keep  both  switches  [I  and  II] 
pressed  simultaneously  for  10 
seconds.
-  The operating  panel  changes  to 
the parameterisation mode (first 
to setting level 1).
-  The  background  lit  logo  flashes 
(once per second). The LEDs valid 
for  the  level  are  lit  on  the  light 
bar:
  LED 1  Level 1
  LED 1+2  Level 2
  LED 1+2+3  Level 3
  LED 1+2+3+4  Level 4
Fig. 3
Key I
Logo
Light
bar
Key II
LED I
LED II
Change setting level
If both keys [I and II] are pressed 
repeatedly  within  5  seconds,  the 
next level is called. 
-  Level 2 is reached when the logo 
stops flashing. LEDs 1+2 are lit 
on the light bar.
-  Level 3 is reached when the logo 
starts flashing again. LEDs 1+2+3 
are lit on the light bar.
-  Level  4  is  reached  when  the 
logo stops  flashing  again.  LEDs 
1+2+3+4 are lit on the light bar.
Change function
When the  desired  setting level is 
reached,  the  setting  of  the  first 
function  (x.1)  is  displayed  on  the 
light bar (LED 1 is lit or LED flashing 
dark green). 
By pressing key II, it is now possi-
ble to switch between functions. 
-  The LED valid for the level is lit or 
flashes on the light bar:
LED 1  Function x.1
LED 2  Function x.2
LED 3  Function x.3
LED 4  Function x.4
LED 5  Function x.5
LED 6  Function x.6
LED 5+6  Function x.7
 LED 1 2 3 4 5 6
Fig. 6