Installation Guide

Figure 9. Attachment points for ohm readings
Testing
SECTION 6
6.4 Go by the Numbers
Theresistanceshouldbemeasuredfromtheinnercoreoftheyellow(120V)orred(240V)leadwireatoneendtotheinner
coreoftheblackleadwireattheotherend.Makesurethattheprobeoftheohmmeterdoesnottouchthetinnedsheath
wireateitherend.Donotholdthewiresontotheprobeswithyourngers.Evenyourbody’selectricalresistancecan
affectthereadingifyoutouchthemeterpoles.Adigitalmeteriseasiertouseandstronglyrecommended.Verifythatthe
batteriesoftheohmmeteraregood.Setyourohmmetertomeasureresistanceintherangeof0to200Ω.
Forcablesthathaveover200Ωresistance,itmaybenecessarytosettheohmmetertothenexthigherrangeof
measurementtogetanaccurateohmreading.
Three(3)ohmreadingsshouldbetakenforeachWarmlyYoursTempZone™FloorHeatingCableateachstageofthe
installationandrecordedinthetableonthewarrantycardinsection10.RefertoFigure9forinstructionsabouthowto
attachtheohmmeterorPowerMan™totakeeachtypeofreading.
1.CoretoCore:Thisisthereadingbetweenthetwoinnerconductorsontheleadwires.
2.CoretoSheath,Yellow/RedLead:Thisisthereadingbetweentheinnercoreandtheoutergroundsheathonthelead
wire.Thisreadingshouldbeinnity.
3.CoretoSheath,BlackLead:Thisisthereadingbetweentheinnercoreandtheoutergroundsheathontheleadwireat
thenishpointofthecable.Thisreadingshouldbeinnity.
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Core to Core Core to Ground Core to Ground
The ground wire may differ from the images above.
The ground wire may be represented as a additional wire with a stripe.
The testing procedure is still performed the same way.
21