Owner`s manual
LEVEL/FLOW SENSOR INPUT # 3 SETUP:
The third Level/Flow Sensor input is provided to facilitate, digital flow monitoring
water level control, other features using optional sensors.
From the Configuration Setup Menu:
Press DOWN to find the Input 3 Setup menu item.
Press ENTER to select Input 3 Setup.
Press DOWN to view the following options:
Disabled
Digital Flow (ENTER to select pipe size).
Level Sensor
Press ENTER to confirm the selection.
After 10 seconds, the controller will revert to the Configuration Setup Menu.
DISPLAY SYSTEM INFORMATION:
The Display System Info function is used to view firmware revision number and the
system date and time as acquired from the wireless communications link.
From the Configuration Setup Menu:
Press DOWN to find the Display System Info menu item.
Press ENTER to select Display System Info.
Press ENTER at the prompt to confirm the selection.
The System Information will be displayed:
After 10 seconds, the controller will revert to the Configuration Setup Menu.
HARD RESET:
The Hard Reset function performs a power-on reset without changing any user-
modified menu items such as setpoints, alarms, pH calibration, etc.
From the Configuration Setup Menu:
Press DOWN to find the Hard Reset menu item.
Press ENTER to select Hard Reset.
Press ENTER at the prompt to confirm the selection.
The CAT 4000 will reset and perform a diagnostic self-test:
After 10 seconds, the controller will revert to the Configuration Setup Menu.
firmware version 1.8
07-12-05 13:22 (UTC)
Diagnostic
Self Check