Envision Console - 50 Hz Installation Manual CONSOLE - 50 Hz Geothermal/Water Source Heat Pump • R-410A Refrigerant • Commercial 2-5 kW Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance IM1015CN 05/14
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Table of Contents Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Model Nomenclature 1-2 3 4-5 6 7 8 9 10 11 12 13 14 15-16 17 NK S 03 L 6 1 1 C N N B 5 SS C Vintage B – PSC Blower & Aluminum Air Coil C – ECM Blower & Aluminum Air Coil Model NK – Envision Series Console 50Hz Non-Standard Option Details SS – Standard Option Cabinet Configuration C – Chassis Only F – Chassis with Cabinet S – Chassis Slope Top E – Chassis with Extended Slope Top Air Coil/Insulation Option 5 – AlumiSealTM/Extended Ra
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL General Installation Information Safety Considerations WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Flat Top Cabinet NKW02-05 @756B @3BC@< :34B @3BC@< B=> 4 2 3 / 0 5 / 0 47:B3@ 0@/193B 47:B3@ 0@/193B 1 8 6 7 23B/7: 0 23B/7: 0 4@=:/AB71 AB@7> 4@=; 0@=93< B/0 /<2 @3>:/13 =< 0@=93< 3253 =4 :35 /A A6=E
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Slope Top Cabinet NKS02-05 @756B @3BC@< :34B @3BC@< B=> 4 2 3 0 5 / / 0 47:B3@ 0@/193B 47:B3@ 0@/193B 1 23B/7: / 23B/7: 0 8 BE7AB 3FB3<232 B/0 0/19 /<2 4=@B6 C:/AB71 AB@7> 4@=; 0@=93< B/0 /<2 @3>:/13 =< 0@=93< 3253 =4 :35 /A A6=
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Extended Slope Top Cabinet NKE02-05 @756B @3BC@< B=> :34B @3BC@< 4 2 3 0 5 / 47:B3@ 0@/193B / 47:B3@ 0@/193B 1 0 8 7 6 23B/7: / BE7AB 3FB3<232 B/0 0/19 /<2 4=@B6 C:/AB71 AB@7> 4@=; 0@=93< B/0 /<2 @3>:/13 =< 0@=93< 3253 =4 :
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Right Return Controls Detail 6/<2G 0=F 1=/<3: @3;=D3 4=@ /113AA B= 1=B7=B7=< AE7B16 3:31B@71 63/B ;=23 <=@;/: 0=7:3@:3AA AE7B16 =>B7=B7=3@ =< =44 AE7B16 1=<23@3AA=@ /113AA >/<3: @3;=D32 4=@ 1:/@7BG 0=B6 A723A =>B7=B7=:/B3 @3?C7@32 4=@ 2/;>3@ 7
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Right Return Chassis Data = inches (cm) Models 02-03 Models 04-05 37.88 (96.2) 9.38 (23.8) CONTROL PANEL 42.88 (108.9) 8.88 (22.6) 28.5 (72.4) CONTROL PANEL 34.0 (86.4) 1.5 (3.8) 1.5 (3.8) BLOWER ACCESS PANEL BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL COMPRESSOR ACCESS PANEL 1.5 (3.8) 1.5 (3.8) 4.37 (11.1) 4.32 (11.0) FILTER FILTER 10.31 (26.2) 4.5 (11.4) WATER OUT 1/2˝ FPT WATER IN 1/2˝ FPT 11.75 (29.8) 4.5 (11.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Left Return Controls Detail 1=/<3: @3;=D3 4=@ /113AA B= 1=3@ =< =44 AE7B16 :=E D=:B/53 B3@;7B7=B7=B7=B7=B7=< AE7B16 =>B7=@3AA=@ /113AA >/<3: @3;=D32 4=@ 1:/@7BG 0=B6 A723A =>B7=B7
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Dimensional Data - Left Return Chassis Data = inches (cm) Models 02-03 28.5 (72.4) Models 04-05 37.88 (96.2) 9.38 (23.8) 34.0 (86.4) CONTROL PANEL 42.88 (108.9) 8.88 (22.6) CONTROL PANEL 1.50 (3.8) 1.50 (3.8) 1.50 (3.8) 1.50 (3.8) BLOWER ACCESS PANEL BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL COMPRESSOR ACCESS PANEL 4.37 (11.1) 4.32 (11.0) FILTER FILTER 10.31 (26.2) 4.5 (11.4) WATER OUT 1/2˝ FPT WATER IN 1/2˝ FPT 11.75 (26.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Installation Steps Step 1: Unpack Equipment and Inspect for Damage Step 2: Determine Equipment Location • Choose level flooring surface (Correctable with shims. Do not pitch towards drain.) • Location of wall support and fasteners required to secure chassis backplate. • Easy access for both installation and service. • Consider availability and ease of wiring, water piping and condensate drain. • No obstructions to block airflow in front of the unit.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Installation Steps cont. Step 4: Provide Water and Condensate Drain Connections • A two-pipe reverse return piping configuration is recommended as it equalizes the piping circuit lengths and delivers even water flow to each unit. A direct return piping configuration may be used, but it may be difficult to achieve and maintain proper water flow to the units. • An air vent must be installed in the water distribution system.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Installation Steps cont. Step 5: Provide Line Voltage Wiring Step 9: Set Unit Controls • Check unit data plate located on control side of chassis for ampacity and fuse size. • Remove electrical knockouts from chassis backplate. • Run line voltage wiring through knockout and secure wiring to backplate or disconnect. • Locate the “continuous fan/cycle fan” switch within the electrical compartment of the chassis and set to desired position.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Installation Steps cont. Field Converting Console Chassis is normally configured with controls on right end and piping on left end (see Figure 3 top view). In this position panel number 1 would be positioned against wall or back plate. Unit may also be turned 180° against wall or back plate. In this position controls will be on left end and piping on right end panel number 2 would be positioned against wall or back plate.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL System Cleaning and Flushing Cleaning and Flushing Ground Source Loop System Checkout Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Open Loop Ground Water Systems Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Ensure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. .09-.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Electrical Connections General Microprocessor Remote Thermostat Wiring Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Electrical Data ECM Blowers LRA Blower Motor FLA Total Unit FLA 4.1 17.0 2.6 4.9 18.7 2.6 5.9 23.0 6.7 24.0 Compressor Rated Voltage Voltage Min/Max 02 220-240/50/1 198/264 6.4 03 220-240/50/1 198/264 7.6 04 220-240/50/1 198/264 9.2 05 220-240/50/1 198/264 10.5 Model MCC RLA Min Circ Amp Max Fuse/ HACR 6.7 7.7 10/15 7.5 8.8 10/15 2.6 8.5 10.0 15 2.6 9.3 11.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Wiring Schematics CCM - ELECTRONIC THERMOSTAT 220-240/50/1 Compressor S Blue PSC Fan Motor C Brn Grn Red Wht Unit Power Supply 220/50/1 Ground Lug R Handi - Box Blk G Tan (33) Cap White (28) L T2 T1 CC L2 L1 H Brown (26) Black (31) Red (32) White (28) Black(29) Fan Switch Red (30) Black High 4 Black (25) 2 NOTE 1 Blue 220V Black (27) Red 200V Transformer Low RB 5 Brown (26) Red (19) 24V PB 1 Yellow Black/White 2 Mode Sw
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Wiring Schematics cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Wiring Schematics cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Wiring Schematics cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Wiring Schematics cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls Control General Description CCM Control The CCM (Compressor control module) is a more reliable replacement for electro-mechanical control applications. It features a small microprocessor board that handles the lockout function of the unit. A second microporcessor handles the unit mounted thermostat for maintaining accurate room temperature. Residential and commercial applications requiring minimal but reliable controls.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. The user selects either “Heat/Cool” or “Fan Only” on the mode switch, then either “High” or “Low” at the blower speed switch. The temperature can be controlled by rotating the thermostat control knob. Figure 6: Unit Mounted Control Component Sequencing Delays Components are sequenced and delayed for optimum unit performance. Short Cycle Protection The control allows a minimum on or off time of 5 minutes for short cycle protection.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. Optional FX10 Control Random Start A delay of 1 to 120 seconds is generated after each powerup to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss. Emergency Shutdown A field-applied dry contact can be used to place the control into emergency shutdown mode. During this mode, all outputs on the board are disabled.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. Condensate overflow fault ...............................................30 seconds Low pressure fault bypass ................................................... 2 minutes Freeze detection fault bypass ............................................
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. Lockout Mode Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze detection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. capacity compressor output will be enabled and the ECM2 blower will operate in high speed. During the heating cycle the reversing valve will be commanded into the off position. Compressor Minimum On Delay The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of (2) minute each time the compressor output is enabled.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. MUI Alarm History Reporting Control Accessories If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu. Each fault type will be displayed in the history menu with a number between 0 and 3. A reading of 3+ will mean that fault has occurred more than three times in the past. The history menu can be cleared with a power cycle only.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Envision Controls cont. MUI Menu Navigation for Single Compressor - Envision Water-to-Air ECM Maintenance MinClgSetpt 15.5 ºC SW1 OFF MaxHtgSetpt 32.2 ºC SW2 OFF W Coil LoLim1 -1.1 ºC SW3 ON SW4 OFF SW5 OFF SW6 OFF W Coil LoLim2 9.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Unit Startup Electrical Disconnect Motorized Outside Air Damper Field installed on the optional chassis back plate, the console disconnect provides a permanent electrical connection to the main electrical supply branch. Wiring between the disconnect and the unit chassis is field supplied and allows the electrical power source to the chassis to be interrupted for unit servicing.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Unit Startup cont. Before Powering Unit, Check The Following: • • • • • • • • • • • • • • High voltage is correct and matches nameplate. Fuses, breakers and wire size correct. Low voltage wiring complete. Piping completed and water system cleaned and flushed. Air is purged from closed loop system. Isolation valves are open, water control valves or loop pumps wired. Condensate line open and correctly pitched. Transformer switched to 220V if applicable.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Operating Parameters Single Speed Models Entering Water Temp °C Cooling Water Flow l/s/kW Suction Pressure kPa Discharge Pressure kPa Superheat Subcooling Water Temp Rise °C Air Temp Drop °C DB 0.1 876 - 993 1413 - 1551 3-6 6-8 10 - 12 10 - 12 2.9 827 - 965 1276 - 1413 4-8 3-6 4-6 10 - 12 0.1 958 - 1062 1931 - 2068 4-6 4-7 10 - 12 10 - 12 2.9 945 - 1048 1724 - 1862 5-7 4-6 4-6 10 - 12 0.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Pressure Drop Pressure Drop (kPa) Model 02 03 04 05 l/s 0°C 10°C 20°C 30°C 0.08 6.9 6.2 5.5 4.8 40°C 4.1 0.11 15.9 15.2 13.8 13.1 12.4 0.16 26.2 25.5 24.1 22.8 21.4 0.09 6.2 5.5 4.8 4.1 3.5 0.15 11.7 10.3 9.7 9.0 7.6 0.22 20.7 18.6 17.2 16.6 15.2 0.13 11.7 11.0 10.3 9.7 9.0 0.19 22.8 22.1 20.7 20.0 19.3 0.25 28.3 27.6 26.9 25.5 24.8 0.13 11.7 11.0 10.3 9.7 9.0 0.22 25.5 24.8 24.1 22.8 22.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL DEALER: PHONE #: DATE: PROBLEM: MODEL #: Startup/Troubleshooting Form SERIAL #: COOLING CYCLE ANALYSIS kPa = SAT °C °C Unit Amp Draw: °C AIR COIL Loop: Open Closed Line Voltage: °C SUCTION COMPRESSOR REVERSING VALVE COAX EXPANSION VALVE SOURCE DISCHARGE °C °F LIQUID LINE SAT °C kPa = °C °C kPa kPa Superheat BRINE IN Subcooling BRINE OUT Heat of Extraction/Rejection = l/s x 4.2 (4.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Preventive Maintenance Water Coil Maintenance Condensate Drain 1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight. 2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL Revision Guide Pages: Description: Date: By: All Updated With Aluminum Air Coils 21 May 2014 DS 43 Added Revision Guide 21 May 2014 DS 43
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com IM1015CN 05/14 Product: Type: Size: Document: Envision Series Console - 50 Hz Geothermal/Water Source Heat Pump Commercial 2-5 kW Installation Manual ©2014 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice.