Instruction Manual

36
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
Maintenance
MinClgSetpt 15.5 ºC
MaxHtgSetpt 32.2 ºC
W Coil LoLim1 -1.1 ºC
W Coil LoLim2 9.4 ºC
TmpOccTime 120 min
Rev Vlv Default Heating
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -18 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 Action On Fan
SW1 OFF
SW2 OFF
SW3 ON
SW4 OFF
SW5 OFF
SW6 OFF
SW7 ON
SW8 OFF
SW9 OFF
SW10 ON
SW11 OFF
SW12 OFF
ECM
ALARM SUMMARY
^/High Pressure
Alarms
Press right arrow key
one time from
Maintenance Menu
No more than three
speeds should beON
at one time
Alarm #Events
Condensate 0
Hi Pressure 0
Low Pressure 0
Low Temp 0
Bad Sensor 0
Alm-History
NOTE: This FX10 application implements an alarm history which is reset
only by cycling power . This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs
are reset by cycling power, by pressing the “ESC and
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
is enabled by holding the ‘Esc and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing . Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.
MUI Menu Navigation for Single Compressor - Envision Water-to-Air