ENVISION CONSOLE INSTALLATION MANUAL
Control Timing & Fault Recognition Delays
Lead compressor “ON” delay ..........................................90 seconds
(not applicable for single compressor models)
Minimum compressor “ON” time ...................................... 2 minutes
(except for fault condition)
Short cycle delay ..................................................................... 5 minutes
Random start delay .......................................................0-120 seconds
High pressure fault ................................................................. <1 second
Low pressure fault ...............................................................30 seconds
Freeze detection fault ...........................................................30 seconds
Condensate overflow fault ...............................................30 seconds
Low pressure fault bypass ................................................... 2 minutes
Freeze detection fault bypass ............................................ 2 minutes
Optional FX10 Microprocessor
and BAS Interface
The FX10 is a microprocessor based control that not
only monitors and controls the heat pump but also can
communicate any of this information back to the building
automation system (BAS). This means that not only does
the control monitor the heat pump at the unit you can also
monitor and control many the features over the BAS. This
clearly puts the FX10 in a class of its own.
The control will enumerate all fault conditions (HP, LP, CO,
LOC, and Freeze Detection) over a BAS as well as display
them on a medium user interface (MUI). HP, LP, CO and
Freeze Detection faults can all be reset over a BAS. A
Loss Of Charge fault can not be reset or bypassed until
the problem has been corrected. A MUI is invaluable as a
service tool for the building service team.
The unit can be commanded to run by a typical heat
pump thermostat or run based on heating and cooling
set points supplied by a BAS. The control board is wired
with quick connect harnesses for easy field change out
of a bad control board. All ECM2.3 variable blower speed
settings can be changed over a BAS or with a MUI. The
control has an input programmed to enable field installed
emergency heat in the event that the compressor is locked
out. This input can also be commanded on from a BAS
as needed. An alarm history can be viewed through the
MUI and will be held in memory until the unit is power
cycled. Relative humidity can be read by a 0-5VDC
humidity sensor that is displayed over the network. If you
are using an ECM2.3 blower motor the control can enable
dehumidification mode based on a set point in the control.
The dehumidification set point itself can also be changed
over a BAS or with a MUI. Dehumidification mode can also
be enabled by the BAS. Because the FX10 is not factory
configured to read CO
2
levels, contact the factory for
application assistance.
The FX10 control has unused analog and digital inputs
for field installed items such as air temperature, water
temperature, CO
2
or current status switches. The control has
unused binary and PWM outputs that can be commanded
over the BAS for field use. An optional Medium User
Interface (MUI) for control setup and advanced diagnostics
is available with some mounting kits, MUIK1 - Panel mount
version and the MUIK2-Wall mount version.
Zone Sensors
There are two options for zone sensors that can be used
with the FX10 control. Both sensors use a Johnson controls
A99 positive temperature coefficient type sensor. The
TAXXJ02 has a set point adjustment now which will give
the end user a +/- 5°F adjustment from the set point as
well as a push button that can be used for temporary
occupancy. The control leaves the factory set to operate
with a TAXXJ02 sensor and can be changed to read the
TAXXA01 sensor through a building automation system or
with a user interface.
Standard Features
Anti Short Cycle
High Pressure Protection
Low Pressure Protection
• Freeze Detection
Loss Of Charge Detection
• Random Start
Display for diagnostics
Reset Lockout at disconnect or through BAS
2 Accessory outputs
Optional BAS add-on controls
DDC Operation and Connection
Other optional network protocol boards that can be added
to the FX10 are:
Johnson Control N2
• LonWorks
• BACnet
- MS/TP @ 19,200 Baud rate
- Limit devices to 30 on a single trunk line.
Envision Console Controls cont.
.