Installation manual
24
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 265/60/1, ECM Blower
97P618-15 10/13/05
C
HWL
HP
Thermostat
CO
R
C
Y1
O
L1
Y2
G
CC Violet
Violet
RV
FP
W
Pink
Black
Violet
Yellow
Black
Blue
Orange
Orange
Pink
Yellow
Yellow
Pink
Orange
White
Tan
Blue
Not Used
Not Used
Not Used
NOTE 1
Not Used
Not Used
Brown
Gray
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
Not Used
Not Used
FieldSelectionDips -#1 On, #6On, #7On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure> 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pumpswitch off
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
LED Normal Display Mode
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM <100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Current Fault Status
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Inputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
Outputs2
Diagnostic Modes
Not Used
Red
NOTE 4
Status LED PCB
17P503A01 Rev A
SW4
R
R
R
R
R
G
Y
R
T
T
Black
ECM2
Fan Motor
Grn
15 101638
On/Off
PWM
RPM
C2
RPM grnd
P12
P112 3 4 51
Transformer
24V
Blk
Blk/Wh
Yel
Or
Brn
1
2
3
P10
4
5
6
*Green LED not flashing
Notes:
2 - 24V Accessory relay (see SW2 - 3 for description of operation)
4 - When using thermostat TA32E12, SW2 -8 should be inthe ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
3 - Air Flow Configuration Example: SW1 configured for dip 3 as low, dip 5 as
medium, and dip 7 ashigh speed ECM2 fan.
1 - Connection of remote unit that does not have a loop pump for slave operation.
5 - When optional electronicair-filter is installed, power for the electronic air-filter is
provided by P2-2and 24 VAC.
Optional
Electronic
Air-Filter
NOTE 5
Blu
265V
Unit Power
265/60/1
G
Compressor
CC
T2 T1
Cap
Blk
Tan
Blu
L2
L1
C
R
S
Red
240V L2
240V L1
240V L2
P6
Microprocessor
Logic Control
(DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
F1-10A 240V
Fused L2
NO
CR1
COM
CC
1
2
3
4
5
6
7
8
1
2
3
P4
1
2
3C
P2
Down
C
1
2
3
4
5
6
7
Shut
SL1 In
Not
SL1 Out
Used
NOTE 2
Acc Com
Acc NC
Acc NO
1
2
3
P3
123
Main Logic PCB
F1-10A 240V
6
5
4
8
7
P5
12
1
2
9
10
3
4
9
11
2
10
8
1
12
5
3
13
14
15
16
11
G
W
O
R
C
Y1
Y2
LO
On
SW1
1
2
3
4
5
6
7
8
9
10
11
12
On
SW3
On
SW2
1
2
3
4
5
6
7
8
24 VAC / TA32E12
No Htg3 / Htg3
Dehum /Norm
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
2 Speed / 1 Speed
Zone (See Note 7)
No RPM / RPM
ECM, EH (See Note 6)
Must be ON
ECM2
Air Flow
Settings
NOTE 3
1
2
3
4
5
14
13
6
7
NO NC
CR4
COM
NO NC
CR3
COM
Thermistor
Light emitting diode- Green
Relay coil
Capacitor w/ bleedresistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1andF2-
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Legend
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
PSC Fan Speed Relay
PSC Fan Power Relay
LP
CS
Blue
Blue
Current Switch
CS
Black
Black
CS -
Current Switch
6 - SW3-4 should be in theOFF position when using ECM motor and 17P501A01
electric heat boardand should be ON when using ECM2 with 17P514A01
electric heat board.
7 - SW3-2 should be OFF to operate with zone controlsystem and ON to operate
with un-zoned system.