Installation manual

25
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 265/60/1, PSC Blower
97P619-21 10/13/05
240V L2
HWL
240V L1
HP
Thermostat
CO
R
C
Y1
O
L1
Y2
240V L2
G
P6
Microprocessor
Logic Control
(DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
NO NC
CR4
COM
F1-10A 240V
Fused L2
NO
CR1
COM
CC
CC Violet
Violet
RV
FP
1
2
3
4
5
6
7
8
W
1
2
3
P4
Pink
Black
Violet
Yellow
Black
Blue
Orange
Orange
Pink
Yellow
Yellow
Pink
Orange
White
Tan
Blue
Not Used
Not Used
Not Used
1
2
3C
P2
Down
C
1
2
3
4
5
6
7
Shut
SL1 In
Not
SL1 Out
Used
NOTE 2
Acc Com
Acc NC
Acc NO
1
2
3
P3
Not Used
Not Used
Brown
Gray
123
Main Logic PCB
NO NC
CR3
COM
F1-10A 240V
Not Used
Not Used
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F)Lockout
High Pressure > 380PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessormalfunction*
HWL thermistor > 130°F
DHW pump switch off
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
LED Normal Display Mode
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Current Fault Status
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Inputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
Outputs2
Diagnostic Modes
Not Used
Red
NOTE 3
6
5
4
8
7
P5
12
1
2
9
10
3
4
9
11
2
10
8
1
12
5
3
13
14
15
16
11
G
W
O
R
C
Y1
Y2
LO
On
SW1
1
2
3
4
5
6
7
8
9
10
11
12
On
SW3
On
SW2
1
2
3
4
5
6
7
8
24 VAC / TA32E12
No Htg3 / Htg3
Dehum / Norm
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
2 Speed / 1 Speed
Zone (See Note 7)
No RPM / RPM
EH (See Note 6)
Must be ON
ECM2
Air Flow
Settings
1
2
3
4
5
Status LED PCB
17P503A01 Rev A
SW4
R
R
R
R
R
G
Y
R
T
T
Black14
7
Transformer
24V
Blk/Wh
Yel
1
2
3
P10
4
5
6
Unit Power
265/60/1
G
Compressor
CC
T2 T1
Cap
Blk
Tan
Blu
L2 L1
C
R
S
Red
Thermistor
Light emitting diode- Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1andF2-
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIPpackage8position
DIPpackage5position
Hot water pump enable switch
Legend
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
PSC Fan Speed Relay
PSC Fan Power Relay
3
15
16
10
8
P12
Blu
265V
Yellow
Yellow
Black
RB
RB
Blk
Blk
*Green LED not flashing
Notes:
1 - Connection of remote unitthat does not have a loop pump for slave operation.
2 - 24V Accessory relay (see SW2 - 3 for description of operation)
3 - When using thermostatTA32E12, SW2 - 8 should bein the ON position.
When using 24VAC thermostats, SW2 - 8 should be in the OFF position.
4 - When optional electronic air-filter is installed, power for the electronic air-filter is
provided by P2-2and 24 VAC.
C
NOTE 1
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
Optional
Electronic
Air-Filter
NOTE 4
Brn
Wh
Grn
P13
3 Air Flow Settings
H M L
PSC
Fan Motor
P019-034
Cap
Cap
NOTE 5
Wh
Wh
Blk
Blk
5 - Unit may be wired with either example shown. Consult installation manual for
blower speed wiring instructions.
Brn
Wh
Grn
P13
3 2 1 C
PSC
Fan Motor
P010-013
Wh
Blk
4
4 Air Flow Settings
LP
CS
Blue
Blue
13
6
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltagewiring
Optional block
DC Voltage PCB traces
CS - Current Switch
CurrentSwitch
CS
Black
Black
6 - SW3-4 should be inthe OFF position when using the 17P501A01 electric heat board
and should be ON when using the 17P514A01 electric heat board.
7 - SW3-2 should be OFF to operate with zone control system and ON to operate with
un-zoned system.