Installation manual

27
PREMIER INSTALLATION MANUAL
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM <100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
LED Normal Display Mode
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure> 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pumpswitchoff
Current Fault Status
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Inputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
Outputs2
Diagnostic Modes
240V L1
HP
CO
240V L2
Transformer
P6
Microprocessor
Logic Control
(DC Voltage)
Fused L2
R
C
CC-GND
NO
CR2
COM
F1-10A 240V
Fused L2
NO
CR1
COM
CC
CC Violet
Violet
RV
FP
1
2
3
4
5
6
7
8
1
2
3
P4
Black
Violet
Yellow
Black
Blue
Orange
Orange
Yellow
Yellow
Pink
Orange
White
Tan
Blue
Not Used
Not Used
Not Used
1
2
3
C
P2
Down
C
1
2
3
4
5
6
7
Shut
SL1 In
Not
SL1 Out
Used
NOTE 1
Acc Com
Acc NC
Acc NO
1
2
3
P3
Not Used
Not Used
Brown
Gray
123
Main Logic PCB
F1-10A 240V
Not Used
Not Used
Not Used
Red
6
5
4
8
7
P5
12
1
2
9
10
3
4
9
11
2
10
8
1
12
5
3
13
14
15
16
11
OnSW1
1
2
3
4
5
6
7
8
9
10
11
12
OnSW3OnSW2
1
2
3
4
5
6
7
8
24 VAC / TA32E12
No Htg3 / Htg3
Dehum / Norm
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
2Speed/1Speed
Zone (See Note 6)
No RPM / RPM
EH (See Note 7)
Must be ON
ECM2
Air Flow
Settings
1
2
3
4
5
T
Black14
7
Blk/WhYel
24V
Status LED PCB
17P503A01 Rev A
SW4
R
R
R
R
R
G
Y
R
1
2
3
P10
4
5
6
Unit Power
460/60/3
Compressor
P1
G
W
O
R
C
Y1
Y2
LO
Thermostat
R
C
Y1
O
L1
Y2
G
W
NOTE 3
G
3
15
16
10
8
P12
NO NC
CR4
COM
NO NC
CR3
COM
Yellow
RB
Black
RB
Black
White
Capacitor
Brown
White
PSC
Fan Motor
Green
MHL
3Air flow
Settings
Black
Cap
Wh
Brn
Grn
3Airflow
Settings
ML
LI MI
Ora Yel
MI
LI
PSC
Fan Motor
NOTE 4
H
Yellow
Blu
460V
Blk
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
Factory Low voltage wiring
Factory Line voltagewiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Fieldwire lug
Ground
Fuse
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Legend
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
PSC Fan Speed Relay
PSC Fan Power Relay
Notes:
1 - 24V Accessory relay (see SW2 - 3 for description
of operation)
2 - Connection of remote unitthat does not have a
loop pump forslave operation.
3 - When using thermostat TA32E12, SW2 -8 should
be in the ON position. When using 24VAC thermo-
stats, SW2 - 8 should be in the OFF position.
4 - Some fan motors may be terminated and wired
with either example shown. Refer to instructions
on motor to change speeds.
*Green LED not flashing
5 - When optional electronic air-filter is installed,
power for the electronic air-filter is provided by
P2-2 and 24 VAC.
C
NOTE 2
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
Optional
Electronic
Air-Filter
NOTE 5
CC
T1
L1
T2
L2
T3
L3
T1
T2
T3
Blue
Black
Red
Yellow wire to L1 on motor, Orange to M1 on
motor.
Refer to instructions below to change speeds.
-High
- L1 to white side of capacitor, L2 toH on motor.
-Med
- L1 to white side of capacitor, L2 toM on motor,
orange wire to M1 onmotor.
-Low
- L1 to white side fo capacitor, L2 to L on motor,
CS -
Current Switch
LP
CS
Blue
Blue
13
6
CurrentSwitch
CS
Black
Black
6 - SW3 - 2 should be OFF to operate with zone
control system and ON to operatewith un-zoned
system.
7 - SW3-4 should bein the OFF position when using
the 17P501A01 electric heat board and should be
ON when using the 17P514A01 electric heat board.
Wiring Schematics
P Series - Single Speed Wiring Schematic - 460-575/60/3, PSC Blower
97P619-22 10/13/05