Installation manual
33
PREMIER INSTALLATION MANUAL
FACTORY SETUP DIP SWITCHES (SW3)
DIP SWITCH
NUMBER
DESCRIPTION OFF POSITION ON POSITION
SW 3- 1 Single-Speed
Confi gures the control for single-speed compressor
operation and should always be left in the “ON” position.
Two-Speed Operation Single-Speed
Operation
SW 3- 2
Zoned/Finish on Second Stage
Confi gures control to operate with zoned or un-zoned
systems
Zoned Systems Un-Zoned Systems
SW 3- 3 No RPM/RPM
Confi gures the control to monitor the RPM output of an
ECM/ECM2 blower motor. When using IntelliZone with a
PSC fan motor, the control should be confi gured for “NO
RPM” sensing.
PSC Fan/RPM
Monitoring
Disabled
ECM2 Fan/RPM
Monitoring
Enabled
SW 3- 4
AT EH Board and ECM/Premier2 EH Board and ECM2
Confi gures the control to operate with electric heat control
board (17P501A01) and ECM motor or with electric heat
board (17P514A01) and ECM2
Electric Heat Control -
17P501A01
Electric Heat Control -
17P514A01
SW 3- 5 Must be on Future Use Normal
DIP Switch Settings
Factory Setup DIP Switches (SW3)
A fi ve-position DIP switch package on the control allows the fi eld selectable options shown in the table below.