PREMIER INSTALLATION MANUAL
OPERATION LOGIC
DATA
HEATING COOLING
FAN ON SL1 - IN ON
STG1 STG2 STG3 EMERG STG1 STG2
Compressor On On On Off On On
ECM2 Normal Med High High High Med High Low
ECM2 Dehumidify Med High High High Low Med Low
PSC Low High High High Low High
Rev Valve Off Off Off Off On On
Loop Pump On On On Off On On On
DHW Pump On Off Off Off On On
Aux Heater Off Off Staged Staged Off Off
SL 1- Out On On On Off On On
Emerg LED On Off Off On Off Off Off
T-Stat Signal Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G
Operation Logic
Typical Water and Air Temperature Changes
WATER
FLOW RATE
WATER TEMPERATURE CHANGE AIR TEMPERATURE CHANGE
RISE (CLG) DROP (HTG) DROP (CLG) RISE (HTG)
3 GPM/TON 9-12 4-8
15-20 20-35
1.5 GPM/TON 20-26 10-17
UNIT GPM
PRESSURE DROP (PSI)
30° EWT 50° EWT 70° EWT 90° EWT 110° EWT
P010
1.5 2.1 2.0 2.0 1.9 1.8
2.0 3.4 3.2 3.1 3.0 2.9
2.5 5.2 4.9 4.7 4.6 4.5
P013
1.5 2.0 1.9 1.9 1.8 1.7
2.5 4.6 4.4 4.2 4.1 4.0
3.5 8.1 7.7 7.4 7.2 7.0
P019
3.0 1.2 1.2 1.1 1.1 1.1
4.0 2.1 2.0
2.0 1.9 1.8
5.0 3.5 3.3 3.2 3.1 3.0
P022
3.0 1.5 1.4 1.3 1.3 1.3
4.5 3.2 3.1 3.0 2.9 2.8
6.0 6.0 5.8 5.6 5.4 5.2
P028
4.0 1.2 1.2 1.1 1.1 1.1
5.5 2.1 2.0 2.0 1.9 1.8
7.0 3.2 3.1 3.0 2.9 2.8
P034
5.0 2.4 2.2 2.2 2.1 2.0
7.0 3.9 3.7 3.6 3.5 3.4
9.0 6.2 5.9 5.7 5.5 5.3
P040
5.0 1.7 1.6 1.5 1.5 1.5
8.0 3.5 3.3 3.2 3.1 3.0
11.0 6.2 5.9 5.7 5.5 5.3
P046
6.0 2.2 2.1 2.1 2.0 1.9
9.0 4.5 4.3 4.1 4.0 3.9
12.0 7.2 6.8 6.6 6.4 6.2
P056
8.0 2.6 2.5 2.4 2.4 2.3
11.0 4.8 4.6 4.4 4.3 4.1
14.0 7.5 7.2 6.9 6.7 6.5
P066
10.0 3.7 3.5 3.4 3.3 3.2
13.0 6.1 5.8 5.6 5.5 5.3
16.0 9.3 8.9 8.6 8.3 8.1
Water Pressure Drop