PREMIER INSTALLATION MANUAL
OPERATION LOGIC
DATA
HEATING COOLING
FAN ON SL1 - IN ON
STG1 STG2 STG3 EMERG STG1 STG2
Compressor On On On Off On On – –
ECM2 Normal Med High High High Med High Low –
ECM2 Dehumidify Med High High High Low Med Low –
PSC Low High High High Low High – –
Rev Valve Off Off Off Off On On – –
Loop Pump On On On Off On On – On
DHW Pump On Off Off Off On On – –
Aux Heater Off Off Staged Staged Off Off – –
SL 1- Out On On On Off On On – –
Emerg LED On Off Off On Off Off Off –
T-Stat Signal Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G –
Operation Logic
Typical Water and Air Temperature Changes
WATER
FLOW RATE
WATER TEMPERATURE CHANGE AIR TEMPERATURE CHANGE
RISE (CLG) DROP (HTG) DROP (CLG) RISE (HTG)
3 GPM/TON 9-12 4-8
15-20 20-35
1.5 GPM/TON 20-26 10-17
UNIT GPM
PRESSURE DROP (PSI)
30° EWT 50° EWT 70° EWT 90° EWT 110° EWT
P010
1.5 2.1 2.0 2.0 1.9 1.8
2.0 3.4 3.2 3.1 3.0 2.9
2.5 5.2 4.9 4.7 4.6 4.5
P013
1.5 2.0 1.9 1.9 1.8 1.7
2.5 4.6 4.4 4.2 4.1 4.0
3.5 8.1 7.7 7.4 7.2 7.0
P019
3.0 1.2 1.2 1.1 1.1 1.1
4.0 2.1 2.0
2.0 1.9 1.8
5.0 3.5 3.3 3.2 3.1 3.0
P022
3.0 1.5 1.4 1.3 1.3 1.3
4.5 3.2 3.1 3.0 2.9 2.8
6.0 6.0 5.8 5.6 5.4 5.2
P028
4.0 1.2 1.2 1.1 1.1 1.1
5.5 2.1 2.0 2.0 1.9 1.8
7.0 3.2 3.1 3.0 2.9 2.8
P034
5.0 2.4 2.2 2.2 2.1 2.0
7.0 3.9 3.7 3.6 3.5 3.4
9.0 6.2 5.9 5.7 5.5 5.3
P040
5.0 1.7 1.6 1.5 1.5 1.5
8.0 3.5 3.3 3.2 3.1 3.0
11.0 6.2 5.9 5.7 5.5 5.3
P046
6.0 2.2 2.1 2.1 2.0 1.9
9.0 4.5 4.3 4.1 4.0 3.9
12.0 7.2 6.8 6.6 6.4 6.2
P056
8.0 2.6 2.5 2.4 2.4 2.3
11.0 4.8 4.6 4.4 4.3 4.1
14.0 7.5 7.2 6.9 6.7 6.5
P066
10.0 3.7 3.5 3.4 3.3 3.2
13.0 6.1 5.8 5.6 5.5 5.3
16.0 9.3 8.9 8.6 8.3 8.1
Water Pressure Drop