User`s manual

Watlow Series SD 24 Chapter 3 Keys and Displays
Programming Page Overview
[Prog]
[PAgE]
The Programming Page determines what parameters
the user wants to appear on the Operations Page. Se-
lect a parameter for any of the 20 (23 for the profiling
version***) Programming Page locations, P1 to P20
(P23***). These now appear on the Operations Page.
All 20 (23***) locations have parameters selected as
defaults.
To go to the Programming Page, hold down the Infinity
key ˆ, then press the Advance Key , and hold both
down for about six seconds.
• Press the Advance Key to move through the
parameter prompts.
• Press the Up ¿ or Down ¯ keys to change the pa-
rameter value.
Press the Infinity Key ˆ at any time to return to
the Home Page.
Note: The hardware configuration and programming selections
will also determine what parameters appear on the Operations
Page. A Programming Page selection will not appear on the
Operations Page if the parameter is not active.
Note: The Programming Page is not accessible while a profile
is running. ***
Programming Page
[~~P1] Parameter Location 1 (48)
[~~P2] Parameter Location 2 (49)
[~~P3] Parameter Location 3 (50)
[~~P4] Parameter Location 4 (51)
[~~P5] Parameter Location 5 (52)
[~~P6 Parameter Location 6 (53)
[~~P7] Parameter Location 7 (54)
[~~P8] Parameter Location 8 (55)
[~~P9] Parameter Location 9 (56)
[~P10] Parameter Location 10 (57)
[~P11] Parameter Location 11 (58)
[~P12] Parameter Location 12 (59)
[~P13] Parameter Location 13 (60)
[~P14] Parameter Location 14 (61)
[~P15] Parameter Location 15 (62)
[~P16] Parameter Location 16 (63)
[~P17] Parameter Location 17 (64)
[~P18] Parameter Location 18 (65)
[~P19] Parameter Location 19 (66)
[~P20] Parameter Location 20 (67)
[~P21] Parameter Location 21 (68)***
[~P22] Parameter Location 22 (69) ***
[~P23] Parameter Location 23 (47)***
*** Profiling version only
Factory Page Overview
[FAct]
[page]
The Factory Page contains information on diagnostics,
calibration and restore-parameter functions.
To go to the Factory Page, press both the Up ¿ and
Down ¯ keys for about six seconds from the Home
Page.
• Press the Advance Key to move through the
parameter prompts.
• Press the Up ¿ or Down ¯ keys to change the pa-
rameter value of Read/Write (R/W) parameters.
Press the Infinity Key ˆ at any time to return to
the Home Page.
Note: Hardware configuration and programming selections de-
termine what parameters appear on the Factory Page.
Note: The Factory Page is not accessible while a profile is run-
ning. ***
Factory Page
[AMb] Ambient Temperature
[A;mn] Minimum Recorded Ambient Temperature
[A;ma] Maximum Recorded Ambient Temperature
[DSPL] Display Intensity
[A;Ot1] Output 1 Process Value
[A;Ot3] Output 3 Process Value
[rESt] Restore Factory Calibration
[Usr;r] Restore User Settings
[USr;S] Save User Settings
[PrF;r] Restore Profile Settings***
[Prf;S] Save Profile Settings***
[dFLt] Default Parameters
[O;ty1] Output 1 Type
[O;ty2] Output 2 Type
[O;ty3] Output 3 Type
[`S;Id] Software ID
[S;UEr] Software Version
[S;bld] Software Build Number
[PWr] Power Type
[`Sn-] Serial Number 1 (first four digits)
[`Sn_] Serial Number 2 (last four digits)
[tc;50] Thermocouple, 50mV
[tc;00] Thermocouple, 0mV
[tc;32] Thermocouple, 32°F
[`r;15] RTD, 15 ohm
[r;380] RTD, 380 ohm
[``U;1] Input Calibrate, 1.0 Volt
[``U;9] Input Calibrate, 9.0 Volt
[``A;4] Input Calibrate, 4.0 mA
[`A;16] Input Calibrate, 16.0 mA
[O1;1u] Output 1 Calibrate, 1.0 Volt
[O1;9u] Output 1 Calibrate, 9.0 Volt
[O1;4A] Output 1 Calibrate, 4.0 mA
[O1;16] Output 1 Calibrate, 16.0 mA
[03;1u] Output 3 Calibrate, 1.0 Volt
[03;9u] Output 3 Calibrate, 9.0 Volt
[03;4A] Output 3 Calibrate, 4.0 mA
[03;16] Output 3 Calibrate, 16.0 mA
Calibration information for the Series SD controllers is available
in pdf format. Go to www.watlow.com / Literature / Product User
Manuals and search on Series SD Calibration Manual.