PM PI D C on troller 40 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Paqram-
eter ID
Data
Type
&
Read/
Write
No Dis-
played
Alarm (1 to 4)
Alarm Clear Request
Write to this register to
clear an alarm
Clear (1003) 0 Instance 1
Map 1 Map 2
1504 1904
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xD (13)
- - - - 9013 uint
W
No Dis-
played
Alarm (1 to 4)
Alarm Silence Request
Write to this register to
silence an alarm
Silence (1010) 0 Instance 1
Map 1 Map 2
1506 1906
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xE (14)
- - - - 9014 uint
W
No Dis-
played
Alarm (1 to 4)
Alarm Silenced
Write to this register to
silence an alarm
Yes (106)
No (59)
- - - - Instance 1
Map 1 Map 2
1500 1900
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0B (11)
- - - - 9011 uint
R
No Dis-
played
Alarm (1 to 4)
Alarm Latched
Write to this register to
silence an alarm
Yes (106)
No (59)
- - - - Instance 1
Map 1 Map 2
1498 1898
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0A (10)
- - - - 9010 uint
R
[P;Sta]
[oPEr]
Profile Status Menu
Profile Menu appears if:
(PM _ [R, B*, N, E*] _ _ _-_ _ _ _ _ _ _)
* Available with PM8/9 only
* Some parameters in the Profile Status Menu can be changed for the
currently running profile, but should only be changed by knowledge-
able personnel and with caution. Changing parameters via the Pro-
file Status Menu will not change the stored profile but will have an
immediate impact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running pro-
file.
[P;Str]
[P.Str]
Profile Status
Profile Start
Select step to act upon.
1 to 40 1 Instance 1
Map 1 Map 2
2520 4340
0x7A (122)
1
1
204 22001 uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM
S: User
Set