User`s guide

Watlow EZ-ZONE
®
PM PID Controller 17 Chapter 2 Install and Wire
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.56 Nm (5.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent
ground loops.
Note:
The control output common termi-
nal and the digital common terminal
are referenced to different voltages
and must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard - Dry contact clo-
sure Digital Inputs shall not be used
in Class I Division 2 Hazardous Loca-
tions unless switch used is approved
for this application.
Warning:
ç
Explosion Hazard – Substitution of
component may impair suitability
for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not discon-
nect while the circuit is live or
unless the area is known to be free
of ignitable concentrations of flam-
mable substances.
Input 1 Thermocouple
-
+
S1
R1
Slot A
2 kΩ maximum source resistance
>20 MΩ input impedance
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The negative lead (usually
red) must be connected to S1.
To reduce errors, the extension wire for thermocouples must be
of the same alloy as the thermocouple.
PM _ _ _ _ _-_ AAAA _ _
Input 1 RTD
2-wire
S1
R1
S1
S3
Slot A
3-wire
T1
S1
R1
S1
S2
S3
Slot A
platinum, 100 and 1,000 Ω @ 0°C
calibration to DIN curve (0.00385 Ω/Ω/°C)
20 Ω total lead resistance
RTD excitation current of 0.09 mA typical. Each
ohm of lead resistance may affect the reading by
0.03°C.
For 3-wire RTDs, the S1 lead (usually white) must
be connected to R1.
For best accuracy use a 3-wire RTD to compensate
for lead-length resistance. All three lead wires must
have the same resistance.
PM _ _ _ _ _-_ AAAA _ _
Input 1 Process
-
+
S1
R1
volts
Slot A
-
+
T1
S1
amperes
Slot A
0 to 20 mA @ 100 Ω input impedance
0 to 10VÎ (dc) @ 20 kΩ input impedance
0 to 50 mVÎ (dc) @ 20 kΩ input impedance
• scalable
PM _ _ _ _ _-_ AAAA _ _
Input 1 Potentiometer
S1
R1
Slot A
CW
CCW
Use a 1 kΩ potentiometer.
PM _ _ _ _ _-_ AAAA _ _