User`s guide

Watlow EZ-ZONE
®
PM PID Controller 69 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Function Key (1 to 2)
Action Function
Program the EZ Key to
trigger an action.
Functions respond to a
level state change or an
edge level change.
[none] None (61)
[usr;r] User Set Restore,
edge triggered (227)
[P;LoC] Keypad Lockout,
level triggered (217)
[ALM] Alarm Reset,
edge triggered (6)
[`SiL] Silence Alarms,
edge triggered (108)
[`AoF] Control Loops Off
and Alarms to Non-alarm
State, level triggered
(220)
[`F;AL] Force Alarm To Oc-
cur, level triggered (218)
[idLE] Idle Set Point,
level triggered (107)
[tUnE] Tune, edge trig-
gered (98)
[MAn] Manual Mode,
level triggered (54)
[`oFF] Switch Control
Loop Off, level triggered
(90)
[`t;da] TRU-TUNE+
®
Dis-
able, level triggered (219)
[P;diS] Profile Disable,
level triggered (206)
[P;hoL] Profile Hold/
Resume, level triggered
(207)
[ProF] Start Profile, edge
triggered (196)
[P;StS] Profile Start/Stop,
level triggered (208)
[s;stp] Start Step (1077)
None Instance 1
Map 1 Map 2
1364 1604
Instance 2
Map 1 Map 2
1384 1624
0x6E (110)
1 to 2
3
138 10003 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Function Instance
Select which instance the
EZ Key will affect. If only
one instance is available,
any selection will affect it.
0 to 4 0 Instance 1
Map 1 Map 2
1364 1606
Instance 2
Map 1 Map 2
1384 1626
0x96 (110)
1 to 2
4
139 10004 uint
RWES
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F] °F (30)
[```C] °C (15)
°F Instance 1
Map 1 Map 2
1838 2308
0x67 (103)
1
5
110 3005 uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50] 50 Hz (3)
[``60] 60 Hz (4)
60 Hz Instance 1
Map 1 Map 2
886 1006
0x6A (106)
1
4
89 1034 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set