EZ-ZONE® PM Express User's Guide L I M I T L I M I T RESET RESET L I M I T RESET Limit Controller TOTAL CUSTOMER SATISFACTION 3 Year Warranty ISO 9001 Registered Company Winona, Minnesota USA 1241 Bundy Boulevard., Winona, Minnesota USA 55987 Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com 0600-0066-0000 Rev. E April 2013 Made in the U.S.A.
Safety Information We use note, caution and warning symbols throughout this book to draw your attention to important operational and safety information. A “NOTE” marks a short message to alert you to an important detail. A “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.
Technical Assistance You can get assistance from your local Watlow representative (see back cover), send an email with your questions to: wintechsupport@watlow.com or dial +1 (507) 494-5656 between 7 a.m. and 5 p.m. Central Standard Time (CST) and ask for an Applications Engineer. Please have the following information available when calling: • Complete model number • All configuration information • User's Manual • Factory Page The EZ-ZONE PM Controller User’s Guide is copyrighted by Watlow Electric, Inc.
Installation and Wiring 1/32 DIN (PM3) Dimensions 15.9 mm (0.63 in) 101.6 mm (4.00 in) 31.2 mm (1.23 in) 53.3 mm (2.10 in) Side 30.9 mm (1.22 in) Front Top 1/32 DIN (PM3) Recommended Panel Spacing 44.96 to 45.47 mm (1.77 to 1.79 in) 22.2 to 22.5 mm (0.87 to 0.89 in) 21.6 mm (0.85 in) minimum 21.6 mm (0.
1/16 DIN (PM6) Dimensions 15.8 mm 53.3 mm (0.62 in) 101.6 mm (2.10 in) (4.00 in) 53.3 mm (2.10 in) Side Front 51.2 mm (2.02 in) Top 1/16 DIN (PM6) Recommended Panel Spacing 44.96 to 45.47 mm (1.77 to 1.79 in) 44.96 to 45.47 mm (1.77 to 1.79 in) panel thickness 1.53 to 9.52 mm (0.060 to 0.375 in) 21.6 mm (0.85 in) minimum 21.5 mm (0.
1/8 DIN (PM8) Vertical Dimensions 15.75 mm (0.62 in) 53.34 mm 1.52 mm (0.06 in) (2.10 in) 100.33 mm (3.95 in) 54.8 mm (2.16 in) 10.16 mm (0.40 in) 30.73 mm (1.21 in) 101.60 mm (4.00 in) 1/8 DIN (PM8) Vertical - Recommended Panel Spacing 44.96 to 45.60 mm (1.77 to 1.79 in) 92.00 to 92.80 mm (3.62 to 3.65 in) panel thickness 1.53 to 9.52 mm (0.060 to 0.375 in) EZ-ZONE PM Limit Express • 6 • 21.6 mm (0.85 in) Minimum 21.6 mm (0.
1/8 DIN (PM9) Horizontal Dimensions 15.75 mm (0.62 in) 100.33 mm (3.95 in) 1.52 mm (0.06 in) 53.8 mm (2.16 in) 53.34 mm (2.10 in) 10.16 mm (0.40 in) 30.73 mm (1.21 in) 101.60 mm (4.00 in) 1/8 DIN (PM9) Horizontal Recommended Panel Spacing 92.00 to 92.80 mm (3.62 to 3.65 in) 44.96 to 45.6 mm (1.77 to 1.79 in) panel thickness 1.53 to 9.52 mm (0.060 to 0.375 in) 21.6 mm (0.85 in) Minimum 21.6 mm (0.
Dimensions 1/4 DIN (PM4) Dimensions 15.75 mm (0.62 in) 100.33 mm (3.05 in) 1.52 mm (0.06 in) 100.33 mm (3.95 in) 12.70 mm (0.50 in) 30.73 mm (1.21 in) 100.84 mm (3.97 in) 92.00 to 93.0 mm (3.62 to 3.65 in) 92.00 to 93.0 mm (3.62 to 3.65 in) 21.6 mm (0.85 in) Minimum panel thickness 1.53 to 9.52 mm (0.060 to 0.375 in) 21.6 mm (0.
Installation the ridges on the sides of the controller. Each tooth is staggered at a different depth from the front so that only one of the tabs, on each side, is locked onto the ridges at a time. Removing the Mounted Controller from Its Case CASE BEZEL 1. From the controller's face, pull out the tab on each side until you hear it click. RETENTION COLLAR PANEL GASKET 1. Make the panel cutout using the mounting template dimensions in this chapter. Insert the case assembly into the panel cutout.
Terminal Definitions Slot C Terminal Function Model 98 99 power input: ac or dc+ power input: ac or dc- PM _L_ _ _ - AAAAB _ _ CF CD CE Standard Bus EIA-485 common Standard Bus EIA-485 T-/RStandard Bus EIA-485 T+/R+ PM _L_ _ _ - AAAAB _ _ S2 (RTD) or current +, S3 (RTD), thermocouple -, current - or volts -, thermistor S1 (RTD), thermocouple + or volts +, thermistor Universal Sensor input 1: all configurations Slot A Input 1 T1 S1 R1 Outputs 1 Terminal Function Configuration 2 X1 W1 Y1 commo
Note: In the graphics below notice that the Slot A connector does not show labeling for the outputs. Labeling for Slot A outputs is based on the controller part number.
Ó Warning: Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life. Note: Maximum wire size termination and torque rating: • 0.0507 to 3.30 mm2 (30 to 12 AWG) singlewire termination or two 1.31 mm2 (16 AWG) • 0.8 Nm (7.0 lb.-in.
Note: In the drawings below for each input notice that the Slot A connector labeling is identified. Note: When using a 2 wire RTD, jumper S1 and T1 together Inputs All inputs shown below represent input 1 (the only input) and are to be connected to slot A of the Limit Control.
Outputs Please note all outputs are connected exclusively to slot A. Output availability is based on the part number of your Limit Control. Note: In the drawings below for each output notice that the Slot A connector labeling is identified with the corresponding part number below.
Outputs (cont.) Switched DC • 22 to 32VÎ(dc) @ 30mA maximum supply current • short circuit limited to <50 mA • 22 to 32VÎ(dc) open circuit voltage • Use dc- and dc+ to drive external solid-state relay. • DIN-a-mite compatibility is for output 1 only.
Keys & Displays 16th DIN LIMIT Controller Zone Display: When [2onE] (found in the Factory Page) is set to on, indicates the controller zone. [1] to [9] = zones 1 to 9 [A] = zone 10 [E] = zone 14 [b] = zone 11 [F] = zone 15 [C] = zone 12 [h] = zone 16 [d] = zone 13 Upper Display: On power up, displays the process value, otherwise displays the value of the parameter in the lower display. PM6 ® L I M I T Lower Display: Indicates the current state of the limit [Fail] or [Safe].
Keys & Displays for 1/8th or 1/4 DIN PID Controllers PM9 ® PM8 ® L I M I T L I M I T RESET PM4 ® RESET L I M I T Responding to a Displayed Message An active message will cause the display to toggle between the normal settings and the active message in the upper or left display and [Attn] in the lower or right display. Your response will depend on the message and the controller settings.
Upon power up of the control, using the advance key will scroll through the various prompts found in the Operations Menu. At any point within the Operations menu to return to the default display push the Reset key. Operations Menu Display [`LL;S] [ LL.S] Limit Low Set Point Set the low process value that will trigger the limit. Appears if: Limit sides set to low or both. [`Lh;S] [ Lh.S] Limit High Set Point Set the high process value that will trigger the limit.
Range Defaults are shown bold -1,999.000 to 9,999.000°F or units -1,128.000 to 5,537.000°C Units, 0.0°F or -18.0°C -1,999.000 to 9,999.000°F or units -1,128.000 to 5,537.000°C Units, 0.0°F or -18.0°C -1,999.000 to 9,999.000°F or units -1,128.000 to 5,537.000°C Units, 32.0°F or 0.0°C -1,999.000 to 9,999.000°F or units -1,128.000 to 5,537.000°C Units, 300.0°F or 150.0°C -1,999.000 to 9,999.000°F or units -1,110.555 to 5,555.000°C 0.
To enter the Setup Menu push and hold the up and down arrow keys for approximately 3 seconds. Once there, push the green advance key to scroll through to the prompt of choice and then use the up and down arrow keys to change the range. At any point within the Setup menu to return to the default display push the Reset key. Setup Menu Display LoC [LoC] Parameter Name Description Lockout Menu Set the security clearance level. The user can access the selected level and all lower levels.
Range (Defaults are shown bold) 1 to 5 1 Operations Menu (read only)* 2 Operations Menu (Set point R/W)* 3 Operations Menu (Set point R/W, Control Mode R/W)* 4 Operations Menu R/W access)* 5 Operations Menu and Setup Menu full R/W access *You can change the security level at any level [``tC] Thermocouple [uolT] Volts dc [`b] [`c] [`d] [`e] [`f] B C D E F [`J] [`H] [`n] [`r] [`S] J K N R S [`MA] Milliamps dc [r0;1H] RTD 100 Ω [`t] T [```A] Curve A, [```b] Curve B, [```C] Curve C [CUSt] Custom [```5] 5
To enter the Setup Menu push and hold the up and down arrow keys for approximately 3 seconds. Once there, push the green advance key to scroll through to the prompt of choice and then use the up and down arrow keys to change the range. At any point within the Setup menu to return to the default display push the Reset key. Setup Menu [`loC] Lockout Menu ‰ Setup Menu (cont.) Display Parameter Name Description [`r;hi] [ r.
Range (Defaults are shown bold) -1,999.00 to 9,999.000 °F or Units -1,110.555 to 5,555.000 °C [`oFF] Off, [LiM] Limit*, [ALM] Alarm *Note: Switched DC/Open Collector option should only be used to control an external mechanical relay if Limit function is selected. [`LiM] Limit Note: Output 2 (only) is FM approved as a limit. [both] Both [high] High [LoW] Low 0.001 to 9,999.0°F or units 0.001 to 5,555.0°C Units, 3.0°F or 2°C [`oFF] Off [PR;AL] Process Alarm 0.001 to 9,999.000°F or units 0.001 to 5,555.
To enter the Setup Menu push and hold the up and down arrow keys for approximately 3 seconds. Once there, push the green advance key to scroll through to the prompt of choice and then use the up and down arrow keys to change the range. At any point within the Setup menu to return to the default display push the Reset key. Setup Menu (cont.) Display LoC [LoC] Parameter Name Description Lockout Menu Set the security clearance level. The user can access the selected level and all lower levels.
Range (Defaults are shown bold) 1 to 5 1 Operations Menu (read only)* 2 Operations Menu (Set point R/W)* 3 Operations Menu (Set point R/W, Control Mode R/W)* 4 Operations Menu R/W access)* 5 Operations Menu and Setup Menu full R/W access *You can change the security level at any level [``tC] Thermocouple [uolT] Volts dc [`b] [`c] [`d] [`e] [`f] B C D E F [`J] [`H] [`n] [`r] [`S] J K N R S [`MA] Milliamps dc [r0;1H] RTD 100 Ω [`t] T [```A] Curve A, [```b] Curve B, [```C] Curve C [CUSt] Custom [```5] 5
To enter the Setup Menu push and hold the up and down arrow keys for approximately 3 seconds. Once there, push the green advance key to scroll through to the prompt of choice and then use the up and down arrow keys to change the range. At any point within the Setup menu to return to the default display push the Reset key. Setup Menu [`loC] Lockout Menu ‰ Setup Menu (cont.) Display Parameter Name Description [`r;hi] [ r.
Range (Defaults are shown bold) -1,999.00 to 9,999.000 °F or Units -1,110.555 to 5,555.000 °C [`oFF] Off, [LiM] Limit*, [ALM] Alarm *Note: Switched DC/Open Collector option should only be used to control an external mechanical relay if Limit function is selected. [`LiM] Limit Note: Output 2 (only) is FM approved as a limit. [both] Both [high] High [LoW] Low 0.001 to 9,999.0°F or units 0.001 to 5,555.0°C Units, 3.0°F or 2°C [`oFF] Off [PR;AL] Process Alarm 0.001 to 9,999.000°F or units 0.001 to 5,555.
To enter the Setup Menu push and hold the up and down arrow keys for approximately 3 seconds. Once there, push the green advance key to scroll through to the prompt of choice and then use the up and down arrow keys to change the range. At any point within the Setup menu to return to the default display push the Reset key. Setup Menu Setup Menu (cont.) Display Alarm Latching Turn alarm latching on or off. A latched alarm has to be turned off by the user. Appears if: When alarm type is set to process.
Range (Defaults are shown bold) [nLAt] Non-Latching [`LAt] Latching [`oFF] Off [`Str] Startup [StPt] Set Point [both] Both [`oFF] Off [``on] On [`oFF] Off [``on] On [AC;Pu] Active Process Value [none] None [`Ls;t] Limit State [`Lh;S] Limit High Set Point [`LL;S] Limit Low Set Point [`A;hi] Alarm High Set Point [`A;lo] Alarm Low Set Point [none] None 1-16 1 EZ-ZONE PM Limit Express • 29 • Se tu p Me n u
Specifications Line Voltage/Power • All voltage levels represent minimums and maximums • 85 to 264V~(ac), 47 to 63Hz • 20 to 28VÅ(ac), +10/-15 percent; 50/60Hz, ±5 percent • 12 to 40VÎ(dc) • 10VA maximum power consumption (PM3 and PM6) • 14VA maximum power consumption (PM4, 8 and 9) • Data retention upon power failure via nonvolatile memory • Compliant with SEMI F47-0200, Figure R1-1 voltage sag requirements @ 24VÅ(ac) or higher Environment • -18 to 65°C (0 to 149°F) operating temperature • -40 to 85°C (-40
Specifications (cont.) Thermistor Input (Not included with Universal Input) Thermistor Input Input Type • • • • Max Error @ 25 Deg C Accuracy Range Low Accuracy Range High Units Thermistor, 5K range ±5 0 5000 Ohms Thermistor, 10K range ±10 0 10000 Ohms Thermistor, 20K range ±20 0 20000 Ohms Thermistor, 40K range ±40 0 40000 Ohms 0 to 40KΩ, 0 to 20KΩ, 0 to 10KΩ, 0 to 5KΩ 2.
Specifications (cont.
Declaration of Conformity Series EZ-ZONE® PM WATLOW an ISO 1241 Bundy Blvd. Winona, MN 55987 USA 9001 approved facility since 1996.
How to Reach Us Corporate Headquarters Watlow Electric Manufacturing Company 12001 Lackland Road St. Louis, MO 63146 Sales: 1-800-WATLOW2 Manufacturing Support: 1-800-4WATLOW Email: info@watlow.com Website: www.watlow.com From outside the USA and Canada: Tel: +1 (314) 878-4600 Fax: +1 (314) 878-6814 Latin America Watlow de México S.A. de C.V. Av. Fundición No. 5 Col. Parques Industriales Querétaro, Qro. CP-76130 Mexico Tel: +52 442 217-6235 Fax: +52 442 217-6403 Europe Watlow France Tour d'Asnières.