User`s guide

EZ-ZONE PM Limit Express 21 Setup Menu
Setup Menu
Display Parameter Name Description Range (Defaults are shown bold)
LoC
[LoC]
Lockout Menu
Set the security clearance level. The user
can access the selected level and all lower
levels.
Appears if: Always
1 to 5
1 Operations Menu (read only)*
2 Operations Menu (Set point R/W)*
3 Operations Menu (Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access)*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level
[Sen]
[ SEn]
Sensor Type
Set the analog sensor type to match the
device wired to this input.
Appears if: Always.
[``tC]Thermocouple [`MA]
Milliamps dc
[uolT]Volts dc [r0;1H]RTD 100 Ω
[Lin]
[ Lin]
Linearization
Set the linearization to match the thermo-
couple type wired to this input.
For example, select[```H]for a type K
thermocouple.
Appears if: Sensor Type is set to Thermo-
couple.
[`b] B [`J] J [`t] T
[`c] C [`H] K
[`d] D [`n] N
[`e] E [`r] R
[`f] F [`S] S
[``t;C]
[t.C]
Thermistor Curve
Select a curve to apply to the thermistor
input.
[```A] CurveA,[```b] CurveB,[```C] CurveC
[CUSt] Custom
[``r;r]
[r.r]
Resistance Range
Set the maximum resistance of the thermis-
tor input.
[```5] 5K,[``10] 10K,[``20] 20K,[``40] 40K
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always.
[```0] Whole
[``0;0] Tenths
[`0;00] Hundredths
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always.
[```F] °F
[```C] °C
[`r;Lo]
[ r.Lo]
Limit Set Point - Range Low
Sets the low limit of the set point adjustment
using a T/C and RTD; scales for process
inputs.
Appears if: Always.
-1,999.00 to 9,999.000 °F or Units
-1,110.555 to 5,555.000 °C
0.0