Watlow EZ-ZONE™ Communications 133 Chapter 9 Factory Page
Parameter name
Description
Modbus
(less 40,001
offset)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Diagnostics Menu
Diagnostics Menu
Hardware ID
Display the hardware ID number.
0 r 101
1
1 r
ASCII character string
floating
point
XXX
Diagnostics Menu
Firmware ID
Display the controller's custom firm-
ware revision number.
2 r 101
1
2 r
ASCII character string
floating
point
XXX
Diagnostics Menu
Software Revision
Display this controller's firmware revi-
sion number.
4 r
101
1
3 r
ASCII character string floating
point
XXX
Diagnostics Menu
Software Build
Display the firmware build number.
6 r
101
1
4 r
ASCII character string floating
point
XXX
Diagnostics Menu
User Restore Set
Replace all of this controller's settings
with another set.
24 r/w
101
1
13 r/w
None (61)
User Set 1 (101)
User Set 2 (102)
Factory Default (33)
None integer
XXX
Diagnostics Menu
User Save Set
Save all of this controller's settings to
the selected set.
26 r/w
101
1
14 r/w
None (61)
User Set 1 (101)
User Set 2 (102)
None integer
XXX
Diagnostics Menu
Device Status
Displays "Fail" if the controller sub-
system has failed and the controller
requires repair.
30 r 101
1
16 r
OK (138)
Fail (32)
OK
integer X X X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.
Int.
PID
Lmt.
Chapter 9: Factory Page