User`s manual

Watlow EZ-ZONE™ Communications 73 Chapter 2 Mobbus RTU & TCPWatlow EZ-ZONE™ Communications 73 Chapter 7 Setup Page
Parameter name
Description
Modbus
(less
40,001 off-
set)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Loop
User Failure Action
Select what the controller outputs will do
when the user switches control to manual
mode.
2182 r/w 107
1
12 r/w
Off, sets output power to 0%
(62)
Bumpless, maintains same
output power, if it was less
than 75% and stable, other-
wise 0% (14)
Manual Fixed, sets output
power to Manual Power set-
ting (54)
User, sets output power to
last open-loop set point the
user entered (100)
Off integer X X
Loop
Input Error Failure
Select what the controller outputs will do
when an input error switches control to
manual mode.
2184 r/w 107
1
13 r/w
Off, sets output power to 0%
(62)
Bumpless, maintains same
output power, if it was less
than 75% and stable, other-
wise 0% (14)
Manual Fixed, sets output
power to Manual Power set-
ting (54)
User, sets output power to
last open-loop set point the
user entered (100)
Off integer X X
Loop
Manual Power
Set the manual output power level that will
take effect if an input error failure occurs.
2180 r/w 107
1
11 r/w
Set Point Open Loop Limit
Low to Set Point Open Loop
Limit High (Setup Page)
0.0 floating
point
XX
Loop
Open Loop Detect Enable
Turn on the open-loop detect feature to
monitor a closed-loop operation for the ap-
propriate response.
1922 r/w 151
1
29 r/w
No (59)
Yes (106)
No integer X X
Loop
Open Loop Detect Time
The Open Loop Detect Deviation value must
occur for this time period to trigger an open-
loop error.
1924 r/w 151
1
23 r/w
0 to 3,600 seconds 240 integer X X
Loop
Open Loop Detect Deviation
Set the value that the process must deviate
from the set point to trigger an open-loop
error.
1926 r/w 151
1
24 r/w
-1,999.000 to 9,999.000 10.0 floating
point
XX
Loop
Ramp Action
Select when the controller's set point will
ramp to the defined end set point.
2186 r/w 107
1
14 r/w
Off (62)
Startup (88)
Set Point Change (85)
Both (13)
Off integer X X
Loop
Ramp Scale
Select the scale of the ramp rate.
2188 r/w 107
1
15 r/w
Hours (39)
Minutes (57)
Minutes integer X X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
Underlined parameters are not accessable using a remote user's interface (RUI) or the controller's front panel. They can only be ac-
cessed using communications.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.