Watlow EZ-ZONE™ Communications 87 Chapter 8 Profiling Page
Parameter name
Description
Modbus
(less
40,001
offset)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
Step 1 Menu
Step 1 Parameters
Step 1 Type
Select a step type.
2570
r/w
121
1
1 r/w
Unused Step (50)
Time (143)
Rate (1120)
Soak (87)
Wait For Event (144)
Wait For Process (209)
Wait For Both (210)
Jump Loop (116)
End (27)
Unused
integer X X
Step 1 Parameters
Target Set Point
Select the set point for this step.
2572
r/w
121
1
2 r/w
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
floating
point
XX
Step 1 Parameters
Hours
Select the hours (plus Minutes and Seconds) for a timed step.
2574
r/w
121
1
3 r/w
0 to 99 0 integer
XX
Step 1 Parameters
Minutes
Select the minutes (plus Hours and Seconds) for a timed step.
2576
r/w
121
1
4 r/w
0 to 59 0 integer
XX
Step 1 Parameters
Seconds
Select the seconds (plus Hours and Minutes) for a timed step.
2578
r/w
121
1
5 r/w
0 to 59 0 integer
XX
Step 1 Parameters
Rate
Select the rate for ramping in degrees or units per minute.
2580
r/w
121
1
6 r/w
0 to 9,999.000°F or units
per minute
0 to 5,555.000°C
0.0 floating
point
XX
Step 1 Parameters
Event Output 1
Select whether Event Output 1 is on or off during this step.
2582
r/w
121
1
7 r/w
Off (62)
On (63)
Off integer
XX
Step 1 Parameters
Event Output 2
Select whether Event Output 2 is on or off during this step.
2584
r/w
121
1
8 r/w
Off (62)
On (63)
Off integer
XX
Step 1 Parameters
Wait Event 1
Select the event state that must be satisfied during this step.
Digital input 5 provides the state of this event.
2586
r/w
121
1
9 r/w
Off (62)
On (63)
None (61)
Off integer
XX
Step 1 Parameters
Wait Event 2
Select the event state that must be satisfied during this step.
Digital input 6 provides the state of this event.
2588
r/w
121
1
10 r/w
Off (62)
On (63)
None (61)
Off integer
XX
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is rated for
1,000,000 writes.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.
Int.
PID
Chapter 8: Profiling Page
8
Note: Changes made to profile parameters in the
Profiling Pages will be saved and will also have an
immediate impact on the running profile.
Some parameters in the Profile Status Menu can
be changed for the currently running profile, but
should only be changed by knowledgeable person-
nel and with caution. Changing parameters via
the Profile Status Menu will not change the stored
profile but will have an immediate impact on the
profile that is running.