Chapter 6: Menu and Parameter Reference Series D8 User’s Guide
134 Watlow Anafaze Doc. 0600-3120-2000
Table 6.10 Display Formats
Input Range High
For a process input, enter the high process variable for input
scaling purposes. This value will be displayed when the input
signal is at the level set for Input high signal.
This parameter and the Input high signal parameter together
define a point on the conversion line for the scaling function.
See Setting Up a Process Input on page 88.
Values: Any value between Input range low and the maxi-
mum process variable for the selected display format (see
Table 6.10).
Default: 1000. Decimal placement depends upon the value of
the Disp format parameter.
Decimal Placement for DeviceNet: See Decimal Placement
for Numeric Values on page 59.
DeviceNet Object: Input (64 hex)
Input High Signal
For a process input, enter the input signal level that corre-
sponds to the value for the Input range high parameter. The
high signal is a percentage of the full scale input range.
Values: -99.8 to 999.9 (-998 to 9999) percent of full scale.
This value must be greater than the value for Input low signal.
Values in parentheses are for communications.
Default: 100.0% (1000)
Decimal Placement for DeviceNet: See Decimal Placement
for Percentage Values on page 60.
DeviceNet Object: Input (64 hex)
Display Value
DeviceNet
Value
Minimum
Process
Variable
Maximum
Process
Variable
-999 to 3000 255 -999 3000
-9999 to 30000 0 -9999 30000
-999.9 to 3000.0 1 -999.9 3000.0
-99.99 to 300.00 2 -99.99 300.00
-9.999 to 30.000 3 -9.999 30.000
-.9999 to 3.0000 4 -0.9999 3.0000
l01 Input ranger
high b 1000 ˚F
l01 Input high r
signal b100.0%