Figure 7.4 Input Circuit
Current Inputs
For each current input, you must install a resistor. The value
of the resistor must be correct for the expected input range. In-
stall the resistor in the listed resistor pack (RP) location. Note
the resistor pack locations have three through-holes. Install
the resistor as shown in the illustration below.
Table 7.5 Resistor Values for Current Inputs
Resistor tolerance: ±0.1%
Table 7.6 Resistor Locations for Current In-
puts
Input Range Resistor Value RD
0 to 10 mA 6.0
0 to 20 mA 3.0
Loop
Resistor
Location RD
Loop
Resistor
Location RD
1 RP1 5 RP5
2 RP2 6 RP6
3 RP3 7 RP7
4 RP4 8 RP8
Com
IN-
RC (RTD)
IN+
RD
RP
Analog
Input
Terminal
Internal
RP
+5 Vdc
Reference
To D8
Circuitry
RC (Voltage)
+
-
RP#
RD