User`s guide

Series D8 User’s Guide Chapter 3: Communicating by DeviceNet
Doc. 0600-3120-2000 Watlow Anafaze 65
Figure 3.12 D84 Produced Static Input
Figure 3.13 D84 Consumed Static Output
Figure 3.14 D88 Produced Static Input
Byte Byte Byte Byte Byte Byte Byte Byte
Exception
Status
1 byte
Loop 1 Process Variable
INT (2 bytes)
Loop 2 Process Variable
INT (2 bytes)
Loop 3 Process Variable
INT (2 bytes)
Loop 4 Process Variable
INT (2 bytes)
Loop 1 Set Point
INT (2 bytes)
Loop 2 Set Point
INT (2 bytes)
Loop 3 Set Point
INT (2 bytes)
Loop 4 Set Point
INT (2 bytes)
Loop 1 Heat Output
UINT (2 bytes)
Loop 2 Heat Output
UINT (2 bytes)
Loop 3 Heat Output
UINT (2 bytes)
Loop 4 Heat Output
UINT (2 bytes)
Loop 1 Cool Output
UINT (2 bytes)
Loop 2 Cool Output
UINT (2 bytes)
Loop 3 Cool Output
UINT (2 bytes)
Loop 4 Cool Output
UINT (2 bytes)
Loop 1 Alarm Status
UINT (2 bytes)
Loop 2 Alarm Status
UINT (2 bytes)
Loop 3 Alarm Status
UINT (2 bytes)
Loop 4 Alarm Status
UINT (2 bytes)
Byte Byte Byte Byte Byte Byte Byte Byte
Loop 1 Set Point
INT (2 bytes)
Loop 2 Set Point
INT (2 bytes)
Loop 3 Set Point
INT (2 bytes)
Loop 4 Set Point
INT (2 bytes)
Loop 1 Control
Mode
USINT (1 byte)
Loop 2 Control
Mode
USINT (1 byte)
Loop 3 Control
Mode
USINT (1 byte)
Loop 4 Control
Mode
USINT (1 byte)
Byte Byte Byte Byte Byte Byte Byte Byte
Exception
Status
1 byte
Loop 1 Process Variable
INT (2 bytes)
Loop 2 Process Variable
INT (2 bytes)
Loop 3 Process Variable
INT (2 bytes)
Loop 4 Process Variable
INT (2 bytes)
Loop 5 Process Variable
INT (2 bytes)
Loop 6 Process Variable
INT (2 bytes)
Loop 7 Process Variable
INT (2 bytes)
Loop 8 Process Variable
INT (2 bytes)
Loop 1 Set Point
INT (2 bytes)
Loop 2 Set Point
INT (2 bytes)
Loop 3 Set Point
INT (2 bytes)
Loop 4 Set Point
INT (2 bytes)
Loop 5 Set Point
INT (2 bytes)
Loop 6 Set Point
INT (2 bytes)
Loop 7 Set Point
INT (2 bytes)
Loop 8 Set Point
INT (2 bytes)
Loop 1 Heat Output
UINT (2 bytes)
Loop 2 Heat Output
UINT (2 bytes)
Loop 3 Heat Output
UINT (2 bytes)
Loop 4 Heat Output
UINT (2 bytes)
Loop 5 Heat Output
UINT (2 bytes)
Loop 6 Heat Output
UINT (2 bytes)
Loop 7 Heat Output
UINT (2 bytes)
Loop 8 Heat Output
UINT (2 bytes)
Loop 1 Cool Output
UINT (2 bytes)
Loop 2 Cool Output
UINT (2 bytes)
Loop 3 Cool Output
UINT (2 bytes)
Loop 4 Cool Output
UINT (2 bytes)
Loop 5 Cool Output
UINT (2 bytes)
Loop 6 Cool Output
UINT (2 bytes)
Loop 7 Cool Output
UINT (2 bytes)
Loop 8 Cool Output
UINT (2 bytes)
Loop 1 Alarm Status
UINT (2 bytes)
Loop 2 Alarm Status
UINT (2 bytes)
Loop 3 Alarm Status
UINT (2 bytes)
Loop 4 Alarm Status
UINT (2 bytes)
Loop 5 Alarm Status
UINT (2 bytes)
Loop 6 Alarm Status
UINT (2 bytes)
Loop 7 Alarm Status
UINT (2 bytes)
Loop 8 Alarm Status
UINT (2 bytes)