User`s manual

Appendix
A.8 WATLOW Series 982 User’s Manual
Specifications
Specifications (1306)
Control Mode
Single input, quad output, optional retransmit of set point or process
variable.
Programmable direct- and reverse-acting control outputs.
4-file, 6 steps per file, time/temperature profile or fixed-set-point
control.
Ramp-rate or time-based programming.
Selectable control status following power loss.
Agency Approvals
CE: 89/336/EEC Electromagnetic Compatibility Directive.
EN 50081-2: 1994 Emissions.
EN 50082-2: 1994 Immunity.
73/23/EEC Low Voltage Directive.
EN 61010-1: 1993 Safety.
UL #873, C-UL File #E43684
NEMA 4X
Operator Interface
Dual, four digit LED displays.
Upper: 0.4 inch (10 mm).
Lower: 0.3 inch (8 mm).
Mode, Hold/Run, Display, Up and Down keys.
Accuracy
Calibration accuracy and sensor conformity: ±0.1% of span,
±1 LSD, 77°F ±5°F (25°C ±3°C) ambient and rated line voltage
±10%.
Accuracy span: 1000°F (540°C) minimum.
Temperature stability: ± 0.2°F/°F (0.1°C/°C) change in ambient.
Sensors/Inputs
Contact input for software function select (event input).
Thermocouple Types B, C
2
, D
2
, E, J, K, N, R, S, T and Pt 2
2
.
RTD resolution in 1° or 0.1° RTD scales.
Process variables: 0-20mA, 4-20mA, 0-5VÎ (dc), 1-5VÎ (dc),
and 0-10VÎ (dc).
Slidewire or digital event input options.
Sensor break protection de-energizes system for safety. Latching or
non-latching.
Input Range
Specified temperature ranges represent the controller's operational span.
Thermocouple
Available with basic or universal signal conditioner
Type C
2
32 to 4200°F (0 to 2316°C)
Type D
2
32 to 4200°F (0 to 2316°C)
Type E -328 to 1470°F (-200 to 799°C)
Type J 32 to 1500°F (0 to 816°C)
Type K -328 to 2500°F (-200 to 1371°C)
Type N 32 to 2372°F (0 to 1300°C)
Type T -328 to 750°F (-200 to 399°C)
Pt 2
2
32 to 2543°F (0 to 1395°C)
Available with universal signal conditioner
Type B 1598 to 3300°F (870 to 1816°C)
Type R 32 to 3200°F (0 to 1760°C)
Type S 32 to 3200°F (0 to 1760°C)
RTD Resolution (DIN or JIS)
1° (DIN) -328 to 1472°F (-200 to 800°C)
1° (JIS) -328 to 1166°F (-200 to 630°C)
0.1° (DIN and JIS)
-99.9 to 999.9°F (-73.3 to 537.7°C)
Process
-999 to 9999 units for all: 0-5VÎ (dc); 1-5VÎ (dc); 0-10VÎ (dc);
0-20mA; and 4-20mA.
Input 2 slidewire feedback
100 to 1200.
Output Options
Solid-state relay, Form A, 0.5A @ 24V~ (ac) min., 253V~ (ac) max.,
opto-isolated, burst fire switching. With or without contact
suppression. Off-state output impedance is 20k with RC
suppression, 31M without contact suppression.
Open collector or switched dc signal provides a minimum turn-on
voltage of 3VÎ (dc) into a minimum 500 load; maximum on
voltage not greater than 32VÎ (dc) into an infinite load, isolated.
Electromechanical relay
1
, Form C, 5A @ 120/240V~ (ac), 6A @
28VÎ (dc), 1/8 hp. @ 120V~ (ac), 125VA @ 120V~ (ac). With or
without contact suppression. Off-state output impedance with RC
suppression is 20k.
Process, 0-20mA, 4-20mA into 800 maximum, 0-5VÎ (dc),
1-5VÎ (dc) or 0-10VÎ (dc) into 1k minimum reverse acting,
isolated.
Electromechanical relay
1
, Form A/B, 5A @ 120/240V~ (ac),
6A @ 28VÎ (dc), 1/8 hp. @ 120V~ (ac), 125VA @ 120V~ (ac).
Without contact suppression.
External transmitter power supply, 5, 12 or 20VÎ (dc) @ 30mA.
EIA/TIA-232 communications or EIA/TIA-485, EIA/TIA-422
communications, opto-isolated.
Retransmit: 0-20mA, 4-20mA with 600 max. load impedance, or
0-5VÎ (dc), 1-5VÎ (dc) and 0-10VÎ (dc) with 500 min. load
impedance.
Line Voltage/Power
100-240Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%.
24 to 28Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%.
Fused internally (factory replaceable only) Slo-Blo
®
type (time-lag):
2A, 250V for high voltage versions;
5A, 250V for low voltage versions.
Power consumption 16VA maximum.
Non-volatile memory retains data if power fails.
Operating Environment
32 to 130°F (0 to 55°C).
0 to 90% RH, non-condensing.
Storage Temperature
-40 to 185°F (-40 to 85°C).
Terminals
#6 compression universal head screws, accepts 28-14 gauge wire.
Controller Weight
1.0 lb (0.45 kg).
Shipping Weight
3.01 lbs (1.35 kg).
Sample/Update Rates
1 input: 10Hz.
2 inputs: 5Hz.
Retransmit: 1Hz.
Remote set point: 1Hz.
PID: 10Hz.
Control outputs: 10Hz.
Alarm outputs: 1Hz.
Display: 2Hz.
Resolution
Inputs: 16 bits.