[``JL] Jump-loop Step (JL) : The following parameters are associated with
the jump-loop step. When StEP = 1, JL will not appear.
[``JF] Jump File: Jumps to the selected file and step (see Jump Step, below),
when the jump file value is not equal to current file. If the jump file value
equals the current file, only steps less than the current program step are
valid selections for a jump step. Changing the jump file value defaults the
jump step to 1. This is a zero-time step.
Range: 1 to 4
Default: current file
[``JS] Jump Step: Jumps backwards to any step in your file, if the jump file
value equals the current file (see Jump File, above). Otherwise you can
jump to any valid step number. This is a zero-time step.
Range: 1 to 6
Default: 1
[``JC] Jump Count: The number of times the Series 981/982 jumps to the
step specified by the JS (jump step) parameter. 0 = infinite number of
jumps.
Range: 0 to 255
Default: 0
[LFiL] Link File (LFiL): The following parameter is associated with the
link file step. When StEP = 1, LFiL will not appear.
[LFiL] Link File: Selects the file to link to. This is a zero-time step. It will not
be shown in the run menu. The control advances to the first step of the
file to be linked to.
Range: 1 to 4
Default: 1
[`End] End Step (End) : The following parameter is associated with the
end step.
[`End] End: Selects the state of the control and auxiliary outputs when a profile
is ended. When HoLd is selected, the control and auxiliary outputs are
enabled and maintain the same state as in the last set point and/or soak
step before the End step was encountered. When selected as OFF, the
control and auxiliary outputs will be disabled and OFF is shown in the
lower display.
Range: HoLd or OFF
Default: HoLd