Manual
Add Increment and Decrement Buttons 
This example assumes you have created a window in a project that is configured to communicate with a 
Watlow Controller and that window is open in EZwarePlus. 
To add a button that increments the set point: 
1)  On the Objects menu, 
click Button then 
choose Set Word. 
2)  Click the General tab. 
3)  In Description type 
Increment Set Point. 
4)  For PLC name choose 
Modbus RTU Master 
or Modbus TCP/IP 
Master. 
5)  Click Setting… 
6)  For Device type 
choose 4x. 
7)  For Address enter the 
address of the User Set 
Point for your 
controller. 
8)  Select the data type for 
the parameter in the 
field below the 
Address field. 
9)  Click OK. 
10)  In Attribute for Set 
Style choose Press and 
hold increment 
(JOG++). 
 (015) 
For this controller… 
This 
parameter… 
Enter this 
Address*… 
Choose this 
Data Type… 
RMCxxxx-xxxxxxx 
Closed Loop 
Set Point 
(Read/Write) 
2501 
32-bit Float 
RMHx-xxxx-x1xx 
5221 
32-bit Float 
PMxxxxx-xxxxxxx 
2161 
32-bit Float 
STxx-xxMx-xxxx 
22 
32-bit Float 
ST via RUI Gateway 
2161 
32-bit Float 
Other Controllers 
Consult the controller manual. 
*These addresses have already been changed to the absolute form required 
for EZwarePlus by adding 1 to the value listed in the Watlow manual. Enter 
them as listed. 
11)  Set Inc. value to 1. 
12)  Set Upper Limit to 100 or a value that is safe for your controller’s set point. 
13)  Set JOG delay to 0.5 seconds. 
14)  Click the Shape tab. 
15)  Check Use shape. 