•  In Comment type a 
description of the data 
to be copied such as 
“PV 1”. 
•  For Address type 
choose Word. 
•  For Interval choose a 
value that is the same as 
or less than the amount 
of time you want 
between data samples. 
•  In No. of words type 
word size of the 
parameter’s data type. 
See table. 
•  For Source address 
PLC name choose 
Modbus RTU Master or 
Modbus TCP/IP 
Master. 
•  For Source address 
device type choose 4x. 
•  In Source address 
Address type the 
address of the parameter 
to be logged. 
(042) 
Data Type 
No. of words 
Float 
2 
16-bit integer 
1 
32-bit integer 
2 
For this controller… 
This 
parameter… 
Enter this 
Address*… 
Choose this 
Data Type… 
RMCxxxx-xxxxxxx 
Analog Input 1 
Process Value 
361 
32-bit Float 
RMHx-xxxx-x1xxx 
381 
32-bit Float 
PMxxxxx-xxxxxxx 
361 
32-bit Float 
STxx-xxMx-xxxx 
20 
32-bit Float 
ST via RUI Gateway 
361 
32-bit Float 
Other Controllers 
Consult the controller manual. 
*These addresses have already been changed to the absolute form required 
for EZwarePlus by adding 1 to the value listed in the Watlow manual. Enter 
them as listed.
•  For Destination address PLC name choose the OIT (“Local HMI” by default). 
•  For Destination address device type choose LW. 
•  In Destination address Address type the local address at which to save the data to be logged. 
Note: Pick a range of addresses with room to store all the data that must be displayed. For example, use 
200 for the first parameter to be logged then for each additional parameter increment the address by 
the size in words of the previous data. For example, typically you log floats such as process 
variables and set points which each require two words to store. In that case if the first process 
variable is copied to 200, set the next parameter to copy to 202 so on. In this example, a process 
variable, a set point and the heat output power are logged. 
•  Click OK. 