Owner manual

122 CLS Users Guide
Appendix A: Ramp Soak
Copying the Setup from Another Profile
Use this menu to setup similar profiles quickly, by copying a profile to
another one.
Selectable Values:
A to Q.
Editing the tolerance Alarm Time
Use this menu to set a tolerance time that applies to the entire profile.
When the segment goes out of tolerance,
The segment goes into tolerance hold
The segment timer holds
The loops single loop display shows TOHO (Tolerance Hold)
When the segment has been out of tolerance for more than the tolerance
alarm time,
The controller goes into tolerance alarm
The tolerance timer resets
You must acknowledge the tolerance alarm by pressing the ALARM
ACK key before you can do any other editing.
Selectable Values:
0:00 to 99:59 (minutes or hours, depending on the
time base setting).
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
COPY SETUP
FROM PROFILE? A
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
A OUT-OF-TOLRNCE
ALARM TIME? 1:00