Owner manual

Installation
CLS Users Guide 33
16 CLS TB-50 Connections.
If you install a Watlow Anafaze Serial digital to Analog Converter
(SDAC), the CLS uses digital output #34 for a clock line. You cannot
use output #34 for anything else when you have an SDAC installed.
* The indicated outputs are dedicated to PID (or control) when enabled
in the loop setup. If one or both of a loops outputs are disabled, the
corresponding digital outputs become available for alarms or ramp/soak
events.
Pin Function PID Output* Pin Function PID Output*
1 +5 Vdc 2 +5 Vdc
3 Digital Ground 4 Digital Ground
5 Not Used 6 Watchdog Timer
7 Pulse Input 8 Global Alarm
9 DIG output 1 Loop 1 heat 10 DIG output 34* Pulse loop cool
11 DIG output 2 Loop 2 heat 12 DIG output 33 Loop 16 cool
13 DIG output 3 Loop 3 heat 14 DIG output 32 Loop 15 cool
15 DIG output 4 Loop 4 heat 16 DIG output 31 Loop 14 cool
17 DIG output 5 Loop 5 heat 18 DIG output 30 Loop 13 cool
19 DIG output 6 Loop 6 heat 20 DIG output 29 Loop 12 cool
21 DIG output 7 Loop 7 heat 22 DIG output 28 Loop 11 cool
23 DIG output 8 Loop 8 heat 24 DIG output 27 Loop 10 cool
25 DIG output 9 Loop 9 heat 26 DIG output 26 Loop 9 cool
27 DIG output 10 Loop 10 heat 28 DIG output 25 Loop 8 cool
29 DIG output 11 Loop 11 heat 30 DIG output 24 Loop 7 cool
31 DIG output 12 Loop 12 heat 32 DIG output 23 Loop 6 cool
33 DIG output 13 Loop 13 heat 34 DIG output 22 Loop 5 cool
35 DIG output 14 Loop 14 heat 36 DIG output 21 Loop 4 cool
37 DIG output 15 Loop 15 heat 38 DIG output 20 Loop 3 cool
39 DIG output 16 Loop 16 heat 40 DIG output 19 Loop 2 cool
41 DIG output 17 Pulse loop heat 42 DIG output 18 Loop 1 cool
43 DIG input 1 44 DIG input 2
45 DIG input 3 46 DIG input 4
47 DIG input 5 48 DIG input 6
49 DIG input 7 50 DIG input 8