Owner manual

38 CLS Users Guide
Installation
16 CLS Scaling Values
For linear mVdc, Vdc, and mAdc ranges, use 0.1% tolerance resistors.
Higher tolerances may cause significant errors. Correct any errors due
to resistor tolerance with the CLS built-in linear scaling. You can also
install other components (like capacitors) for signal conditioning; please
consult Watlow Anafaze for more information.
The next table shows scaling resistor values.
The next table shows the location of RC and RD on the analog input
board. (The analog input board is the upper board of the two-board set.)
A wire trace on the printed circuit board jumpers the RC position. When
you place a resistor in the RC position, cut the wire trace that connects
the two resistor terminals.
Input Range RC RD
All T/C, 0-60 mV DC Jumper
0-10 mA DC
0-20 mA DC
Jumper
Jumper
6.0 ohms
3.0 ohms
0-100 mV
0-500 mV
499 ohms
5.49 Kohms
750 ohms
750 ohms
0-1 VDC
0-5 VDC
0-10 VDC
0-12 VDC
6.91 Kohms
39.2 Kohms
49.9 Kohms
84.5 Kohms
422.0 ohms
475.0 ohms
301.0 ohms
422.0 ohms
Loop # RC RD Loop # RC RD
1 R58 R42 9 R57 R41
2 R56 R40 10 R55 R39
3 R54 R38 11 R53 R37
4 R52 R36 12 R51 R35
5 R50 R34 13 R49 R33
6 R48 R32 14 R47 R31
7 R46 R30 15 R45 R29
8 R44 R28 16 R43 R27
Analog
IN +
RD
CLS Measurement
Circuitry
Analog
Input
Terminals
RC
Common
IN +