Owner manual

Using the CLS
CLS Users Guide 51
WARNING
Pressing the No key on power up will clear the RAM mem-
ory and reinitialize the CLS' factory default values.
To do a No Key Reset, power down the controller, press and hold the No
key, and power up the controller while holding the No key. A No Key
Reset is appropriate:
After you change the EPROM. (See Chapter 6: Troubleshooting.)
In some cases when troubleshooting (see Chapter 6: Troubleshoot-
ing).
When you install the controller.
Back
The
Back
key works like an escape key. Press it to:
Abort editing.
Return to a previous menu.
Switch between Bar Graph, Single Loop, and Job Control displays.
Enter
Press
Enter
to:
Store data or menu choices after editing and go on to the next menu.
Start scanning mode (if pressed twice).
Change SP
Press this key to change the loop setpoint.
Man/Auto
Press the
Man/Auto
key to:
Toggle a loop between manual and automatic control.
Adjust the output power level of loops in Manual control.
Automatically tune a loop.