70 CLS Users Guide
Setup
Set up Loop Input
The Set up Loop Input main menu lets you access menus which change
parameters related to the loop input:
Input type
Input units
Input scaling and calibration
Input filtering
The next section explains how to use the Input menus to configure your
controller.
Below is the setup inputs menu tree. Notice the default values inside the
boxes.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
SETUP LOOP 02
INPUT ?
Setup Loop Inputs?
Input Type? J T/C
Pulse Sample Time? 1s
(only for pulse input)
Loop Name?
Input Units?
º
F
Input Readin
g
Offset?
º
F (only for T/C inputs)
Disp Format?-999 to
3000
(only for linear)
Input Scalin
g
Hi PV?
1000 (linear & pulse)
Input Scalin
g
Hi RDG?
100.0%FS
(linear&pulse)
Input Scalin
g
Lo PV? 0
(linear & pulse)
Input Scalin
g
Lo RDG?
.0%FS (linear & pulse)
Input Filter?
3 Scans