Owner's manual

EZ-ZONE PM Limit Express 13 Install & Wiring
Note:
In the drawings below for each input notice that the Slot A connector labeling is identified.
Note:
When using a 2 wire RTD, jumper S1 and T1 together
Inputs
All inputs shown below represent input 1 (the only input) and are to be connected to slot A of the Limit Control.
Process Volts and Amperes
4 to 20 mA @ 100 Ω input impedance
0 to 10VÎ (dc) @ 20 kΩ input impedance
Scalable
Resistance Temperature Detector (RTD)
Platinum, 100 Ω @ 0°C
Calibration to DIN curve (0.00385 Ω/Ω/°C)
20 Ω total lead resistance
RTD excitation current of 0.09 mA typical. Each
ohm of lead resistance may affect the reading by
0.03°C.
For 3-wire RTDs, the S1 lead must be connected
to R1.
For best accuracy use a 3-wire RTD to compen-
sate for lead-length resistance. All three lead
wires must have the same resistance.
Thermocouple
2 KΩ maximum source resistance
>20 MΩ input impedance
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The nega-
tive lead must be connected to S1.
To reduce errors, the extension wire for thermo-
couples must be of the same alloy as the thermo-
couple.
Thermistor
>20 MΩ input impedance
3 microampere open-sensor detection
-
+
Thermocouple
S1
R1
T1
S1
R1
S1
S2
S3
RTD
2 or 3 Wire
-
+
-
+
S1
R1
T1
S1
Process
Volts
Process
Amperes
Thermistor
S1
R1